A UPS emergency
CAUTION
All power to the critical load is lost when the REPO switch is activated in the following step. You should use this feature only when you want to
NOTE
The following instructions are for the Eaton
To use the REPO switch:
1.Press the REPO pushbutton switch.
The input, output, and bypass backfeed contactors open, the battery breaker or disconnect is tripped, and the power module is turned off immediately, without asking for verification.
CAUTION
Do not attempt to restart the system after Load Off until the cause of the shutdown has been identified and cleared.
2.To restart the UPS after using the REPO pushbutton, reset the REPO switch and then follow the procedure in paragraph 5.3.1 or 5.3.2.
63 | UPS 450 - 550 kVA (2x225 - 2x275 kVA) | 1027574 |
| User’s and Installation Guide | Revision B |