Note Remote EPO switch rating is 24 Vdc, 1 A minimum.

Note Remote EPO normally-open and normally-closed return terminals are separated on the terminal board, but are electrically in common.

Figure 3-13. Normally-Open remote EPO switch wiring

10.If you are installing multiple remote EPO switches, wire additional switches in parallel with the first remote EPO.

11.If required, install wiring from the remote EPO switch to the trip circuitry of the upstream protective devices. A normally-open (NO) contact is provided between terminals 6 and 7 of the remote EPO switch, as shown in Figure 3-12. Remote EPO switch wiring must be in accordance with UL Class II requirements.

12.When all wiring is complete, reinstall the small top internal safety shield panel and secure with the cabinet mounted screws.

13.Reinstall the center front panel removed in previous steps and secure with the retained hardware.

14.Figure 3-14 and Figure 3-15 show alternative methods of connecting a remote EPO switch if using another manufacturer’s switch.

Note Remote EPO switch rating is 24 Vdc, 1 A minimum.

Note Remote EPO normally-open and normally-closed return terminals are separated on the terminal board, but are electrically in common.

Figure 3-14. Normally closed remote EPO switch wiring

38

UPS 450 - 550 kVA (2x225 - 2x275 kVA)

1027574

 

User’s and Installation Guide

Revision B