MM DD YYYY HH:MM:SS.hh KYWD MESSAGE <CR> <LF>

Where

Equals

MM

Month (2 digits)

DD

Day (2 digits)

YYYY

Year (4 digits)

HH

Hour (2 digits)

MM

Minute (2 digits)

SS

Second (2 digits)

hh

Hundredths of Second (2 sdigits)

KYDW

Keyword (ALARM, NOTICE, COMMAND, or STATUS)

Message

System Diagnostic Information

<CR>

Carriage Return Character (ASCII 13)

<LF>

Line Feed (ASCII 10)

An alarm message is prefixed by the word “CLEAR” whenever an alarm is entered into the Event History Log with a cleared status.

If a port is operating inTerminal mode and is connected to a computer, you can press [Esc] [H] to print the entire log with a firmware version header.The log in terminal mode is always in english.

MODEL: POWERWARE 9395

CTO: TF12710000000

SERIAL:

MCU DSP:

70.81.14

MCU BOOTLOADER:

80.40

MCU PLD:

1.00

PMF 1 DSP:

80.81.14

PMF 1 BOOTLOADER:

80.40

PMF 1 PLD:

1.00

XSLOT CAN BRIDGE:

0.00

CSB DSP:

70.81.14

CSB BOOTLOADER:

1.12

DISPLAY:

1.06

TIME: 19:17:16 DATE: 03/23/2099

03/16/2099 21:25:20.355 S138: CONTROL POWER ON (PM1)

03/16/2099 21:25:20.515 N011: OUTPUT UNDER OR OVER FREQ (PM1)

03/16/2099 21:25:20.675 S302: EEPS CONFIGURING (PM1)

03/16/2099 21:25:23.475 N267: POWER MODULE CABLE FAIL 15 (PM1)

03/16/2099 21:25:25.180 N271: DC HW AMPS LIMIT (PM1)

03/16/2099 21:25:25.215 N007: INPUT AC UNDER VOLTAGE (PM1)

03/16/2099 21:25:25.850 N011: OUTPUT UNDER OR OVER FREQ OK (PM1)

...

03/23/2099 18:59:20.450 A199: BATTERIES DISCONNECTED (PM1)

ACTIVE ALARMS:

11 NOTICE: OUTPUT UNDER OR OVER FREQ (PM1)

12 ALARM: REMOTE EMERGENCY POWER OFF (MCU)

102 NOTICE: INVERTER L1 CURRENT LIMIT (PM1)

103 NOTICE: INVERTER L2 CURRENT LIMIT (PM1)

104 NOTICE: INVERTER L3 CURRENT LIMIT (PM1)

Figure 7-3. Sample Event History Log

69

UPS 450 - 550 kVA (2x225 - 2x275 kVA)

1027574

 

User’s and Installation Guide

Revision B