Where | Equals |
MM | Month (2 digits) |
DD | Day (2 digits) |
YYYY | Year (4 digits) |
HH | Hour (2 digits) |
MM | Minute (2 digits) |
SS | Second (2 digits) |
hh | Hundredths of Second (2 sdigits) |
KYDW | Keyword (ALARM, NOTICE, COMMAND, or STATUS) |
Message | System Diagnostic Information |
<CR> | Carriage Return Character (ASCII 13) |
<LF> | Line Feed (ASCII 10) |
An alarm message is prefixed by the word “CLEAR” whenever an alarm is entered into the Event History Log with a cleared status.
If a port is operating inTerminal mode and is connected to a computer, you can press [Esc] [H] to print the entire log with a firmware version header.The log in terminal mode is always in english.
MODEL: POWERWARE 9395
CTO: TF12710000000
SERIAL:
MCU DSP: | 70.81.14 |
MCU BOOTLOADER: | 80.40 |
MCU PLD: | 1.00 |
PMF 1 DSP: | 80.81.14 |
PMF 1 BOOTLOADER: | 80.40 |
PMF 1 PLD: | 1.00 |
XSLOT CAN BRIDGE: | 0.00 |
CSB DSP: | 70.81.14 |
CSB BOOTLOADER: | 1.12 |
DISPLAY: | 1.06 |
TIME: 19:17:16 DATE: 03/23/2099
03/16/2099 21:25:20.355 S138: CONTROL POWER ON (PM1)
03/16/2099 21:25:20.515 N011: OUTPUT UNDER OR OVER FREQ (PM1)
03/16/2099 21:25:20.675 S302: EEPS CONFIGURING (PM1)
03/16/2099 21:25:23.475 N267: POWER MODULE CABLE FAIL 15 (PM1)
03/16/2099 21:25:25.180 N271: DC HW AMPS LIMIT (PM1)
03/16/2099 21:25:25.215 N007: INPUT AC UNDER VOLTAGE (PM1)
03/16/2099 21:25:25.850 N011: OUTPUT UNDER OR OVER FREQ OK (PM1)
...
03/23/2099 18:59:20.450 A199: BATTERIES DISCONNECTED (PM1)
ACTIVE ALARMS:
11 NOTICE: OUTPUT UNDER OR OVER FREQ (PM1)
12 ALARM: REMOTE EMERGENCY POWER OFF (MCU)
102 NOTICE: INVERTER L1 CURRENT LIMIT (PM1)
103 NOTICE: INVERTER L2 CURRENT LIMIT (PM1)
104 NOTICE: INVERTER L3 CURRENT LIMIT (PM1)
Figure69 | UPS 450 - 550 kVA (2x225 - 2x275 kVA) | 1027574 |
| User’s and Installation Guide | Revision B |