Terminal TB1NameDescrition

1

Remote EPO NC

 

2

Remote EPO return

Dry contact used to active remote EPO of UPS.

3

Remote EPO NO

 

4

Remote EPO return

 

5

Battery aux

 

6

Battery aux return

 

7

48 Vdc battery shunt trip +

 

8

48 Vdc battery shunt trip -

 

9

Not used

 

10

Not used

 

Terminal TB2

Name

Descrition

1

Pull chain

Back control for parallel operation.

2

Pull chain return

 

3

Alarm relay NC

 

4

Alarm relay return

General purpose normally-open (NO) and normally-closed

5

Alarm relay NO

(NC) relay contacts.

6

Alarm relay return

 

7

Not used

 

8

Not used

 

9

Not used

 

10

Not used

 

Terminal TB3

Name

Descrition

1

Building alarm 1

Programmable UPS alarm. Activated by a remote dry contact

2

Building alarm 1 return

closure.

3

Building alarm 2

Programmable UPS alarm. Activated by a remote dry contact

4

Building alarm 2 return

closure.

5

Building alarm 3

Programmable UPS alarm. Activated by a remote dry contact

6

Building alarm 3 return

closure.

7

Building alarm 4

Programmable UPS alarm. Activated by a remote dry contact

8

Building alarm 4 return

closure.

9

Building alarm 5

Programmable UPS alarm. Activated by a remote dry contact

10

Building alarm 5 return

closure.

Table 3-1. TB1, TB2, and TB3 interface connections

32

UPS 450 - 550 kVA (2x225 - 2x275 kVA)

1027574

 

User’s and Installation Guide

Revision B