Terminal TB1 | Name | Descrition | |
1 | Remote EPO NC |
| |
2 | Remote EPO return | Dry contact used to active remote EPO of UPS. | |
3 | Remote EPO NO | ||
| |||
4 | Remote EPO return |
| |
5 | Battery aux |
| |
6 | Battery aux return |
| |
7 | 48 Vdc battery shunt trip + |
| |
8 | 48 Vdc battery shunt trip - |
| |
9 | Not used |
| |
10 | Not used |
|
Terminal TB2 | Name | Descrition | |
1 | Pull chain | Back control for parallel operation. | |
2 | Pull chain return | ||
| |||
3 | Alarm relay NC |
| |
4 | Alarm relay return | General purpose | |
5 | Alarm relay NO | (NC) relay contacts. | |
6 | Alarm relay return |
| |
7 | Not used |
| |
8 | Not used |
| |
9 | Not used |
| |
10 | Not used |
|
Terminal TB3 | Name | Descrition |
1 | Building alarm 1 | Programmable UPS alarm. Activated by a remote dry contact |
2 | Building alarm 1 return | closure. |
3 | Building alarm 2 | Programmable UPS alarm. Activated by a remote dry contact |
4 | Building alarm 2 return | closure. |
5 | Building alarm 3 | Programmable UPS alarm. Activated by a remote dry contact |
6 | Building alarm 3 return | closure. |
7 | Building alarm 4 | Programmable UPS alarm. Activated by a remote dry contact |
8 | Building alarm 4 return | closure. |
9 | Building alarm 5 | Programmable UPS alarm. Activated by a remote dry contact |
10 | Building alarm 5 return | closure. |
32 | UPS 450 - 550 kVA (2x225 - 2x275 kVA) | 1027574 |
| User’s and Installation Guide | Revision B |