Function | Subfunction | Operation |
Maximum Current |
| The Maximum Current Log screen displays the individual log entries, including |
Log |
| the interval date and time frame, the maximum percent of full load during the |
|
| interval, the total time over limit during the interval, and the number of times |
|
| over during the interval. If the individual phase option is selected, the phases |
|
| that exceeded the limit will also be displayed. If no events have occurred, the |
|
| screen will display LOG EMPTY. Press the LOG pushbutton on the Maximum |
|
| Current Log Summary menu bar to display the Maximum Current Log screen. To |
|
| scroll through the individual events, press the up or down arrow pushbuttons |
|
| on the menu bar. To return to the Maximum Current Log Summary screen, press |
|
| the SUMMARY pushbutton on the menu bar. To clear the Maximum Current Log, |
|
| press the RESET pushbutton on the menu bar. |
Maximum Current | Screen 1 | The Maximum Current Log Setup screen 1 displays the current user defined log |
Log Setup |
| settings. If no log settings are configured, the screen will display MAXIMUM |
|
| CURRENT LOG DISABLED. Press the SETUP pushbutton on theMaximum Current |
|
| Log Summary menu bar to display the Maximum Current Log Setup screen 1. |
|
| To return to the Maximum Current Log Summary screen, press the return arrow |
|
| pushbutton on the menu bar. |
|
|
|
| Screen 2 | The Maximum Current Log Setup screen can be used to set up or change the |
|
| time interval, the maximum percent of load, and the calculation method (three- |
|
| phase average or individual phases) log settings. Press the CHANGE pushbutton |
|
| on the Maximum Current Log Setup menu bar to display the Maximum Current |
|
| Log Setup screen 2. Use the up or down arrow pushbuttons to highlight the |
|
| setup function screen desired, then press the SELECT pushbutton to display the |
|
| function screen. To return to the Maximum Current Log Setup screen 1, press the |
|
| return arrow pushbutton on the menu bar. |
| Time Interval Moni- | The Time Interval Monitored Setup screen allows the time duration of the event |
| tored Setup | being monitored to be changed. Select TIME INTERVAL MONITORED from the |
|
| Maximum Current Log Setup screen 2 menu to display the Time Interval Moni- |
|
| tored Setup screen. Use the left or right arrow pushbuttons to select the char- |
|
| acter position. Use the up or down arrow pushbuttons to change the character |
|
| value. Once the new value is entered, press the DONE pushbutton. The Time |
|
| Interval Monitored Setup Save screen is displayed. |
|
|
|
| Time Interval Moni- | The Time Interval Monitored Setup Save screen lets you save the new time |
| tored Save | interval, retry another time interval, or abort the change. Press SAVE, RETRY, or |
|
| ABORT. If SAVE or ABORT is pressed, the action is completed, and the Maximum |
|
| Current Log Setup screen 2 displays. If RETRY is pressed, the Time Interval Moni- |
|
| tored Setup screen is redisplayed. |
| Maximum % of Full | The Maximum % of Full Load Setup screen allows the full load limit of the event |
| Load Setup | being monitored to be changed. Select MAXIMUM % of FULL LOAD from the |
|
| Maximum Current Log Setup screen 2 menu to display the Maximum % of Full |
|
| Load Setup screen. Use the left or right arrow pushbuttons to select the char- |
|
| acter position. Use the up or down pushbuttons to change the character value. |
|
| Once the new value is entered, press the DONE pushbutton. The Maximum % of |
|
| Full Load Setup Save screen is displayed. |
| Maximum % of Full | The Maximum % of Full Load Setup Save screen lets you save the new load limit, |
| Load Save | retry another load limit, or abort the change. Press SAVE, RETRY, or ABORT. If |
|
| SAVE or ABORT is pressed, the action is completed, and theMaximum Current |
|
| Log Setup screen 2 displays. If RETRY is pressed, the Maximum % of Full Load |
|
| Setup screen is redisplayed. |
| Calculation Method | The CalculationMethod Setup screen allows the full load limit of the event being |
| Setup | monitored to be changed. Select CALCULATION METHOD from the Maximum |
|
| Current Log Setup screen 2 menu to display the Calculation Method Setup |
|
| screen. Select CALCULATION METHOD from the Maximum Current Log Setup |
|
| screen 2 menu to display the Calculation Method Setup screen. Use the up or |
|
| down arrow pushbuttons to highlight the calculation method desired, then press |
|
| the SELECT pushbutton. The action is completed, and the Maximum Current Log |
|
| Setup screen 2 displays. To return to the Maximum Current Log Setup screen 1, |
|
| press the return arrow pushbutton on the menu bar. |
1027574 | UPS 450 - 550 kVA (2x225 - 2x275 kVA) | 55 |
Revision B | User’s and Installation Guide |
|