The load off screen appears when the LOAD OFF pushbutton is selected from the main menu bar or System Controls menu bar.This screen allows the LOAD OFF process to be aborted if the LOAD OFF pushbutton was pressed accidentally. Figure
5.3 Operation
5.3.1 Starting the UPS in normal modeTo start the UPS system:
1.If the UPS contains input breaker CB1, verify that input breaker CB1 is open.
2.Close the UPS input feeder circuit breaker.
3.Close the UPS bypass input feeder circuit breaker.
4.Observe the UPS control panel display becoming active, indicating logic power.
5.Press the CONTROLS pushbutton on the main menu bar.The system controls screen appears.
58 | UPS 450 - 550 kVA (2x225 - 2x275 kVA) | 1027574 |
| User’s and Installation Guide | Revision B |