NOTE
If installing, as part of the UPS system, a maintenance bypass without a rectifier input breaker, a minimum of two separate feeds with upstream feeder breakers, or one feed with two upstream feeder breakers, must be provided: one for the UPS and one for the maintenance bypass input. DO NOT use one feed or a single feeder breaker to supply both the UPS and the maintenance bypass.
14 | UPS 450 - 550 kVA (2x225 - 2x275 kVA) | 1027574 |
| User’s and Installation Guide | Revision B |