NOTE If the load requires a neutral, a bypass source neutral must be provided. If the load does not require a neutral and there is no neutral conductor connected at the bypass input, a neutral to ground bonding jumper must be installed. DO

NOT install both a source neutral and a bonding jumper.

Figure 4-5. Powerware 9395 450–550 kVA UPS system, 400 V input and 400 V output dual-feed

46

UPS 450 - 550 kVA (2x225 - 2x275 kVA)

1027574

 

User’s and Installation Guide

Revision B