Emerson MPR25, MPR15 Series user manual Signal Connector

Models: MPR15 Series MPR25

1 120
Download 120 pages 55.76 Kb
Page 29
Image 29
Figure 3 - Signal Connector

Operation 29

Figure 3 - Signal Connector

 

1

- REMOTE EQL

 

2

- SENSING RG +

 

3

- SENSING RC -

 

4

- TEMPORARY RELEASE

1

5

- REMOTE HVSD RESET

6

- REMOTE HVSD

 

7

- RFA NC

 

8

- Not Connected

 

9

- FAN ALARM NC

 

10

- RFA COMMON

 

11

- FAN ALARM COMMON

 

12

- SHUNT +

 

13

- SHUNT -

 

14

- FAN ALARM NO

 

15

- RFA NO

 

16

- GROUND

 

17

- SENSE COMMON

 

18

- SENSE NC

 

19

- SENSE NO

 

20

- Not Connected

25

21

- Not Connected

 

22

- Not Connected

 

23

- Not Connected

 

24

- Not Connected

 

25

- Not Connected

Connector housing:

 

AMP 211149-1

Crimp type pins (24-20 AWG):

 

AMP 66103-1

PCB solder/wire wrap pins:

 

AMP 66460-7

The 'SENSE' alarm contact closes to indicate that the remote sense leads are open.

The signals normally connected to Astec controllers are indicated below.