Emerson MPR15 Series NT5C10BA-1/2, NT5C10BF-1 and NT5C10BP hot standby power shelf, Designation

Models: MPR15 Series MPR25

1 120
Download 120 pages 55.76 Kb
Page 54
Image 54
Table 9 - Standard system application signal cable connections:

54 Installation and start-up procedures

Table 9 - Standard system application signal cable connections:

DESIGNATION

DESCRIPTION

SIGNAL

 

 

ACTIVATES

 

 

 

RG (+) and RC (-)

Sensing Leads

BAT RTN

 

 

 

HVSD

High Voltage Shutdown

 

 

 

 

HVSDR

High Voltage Shutdown Reset

BAT RTN

 

 

 

TR

Remote Inhibit

BAT RTN

 

 

 

EQ

Remote Equalize

BAT RTN

 

 

 

RFA

Rectifier Failure Alarm

Form C contacts

 

 

 

FAN ALM

Fan Failure Alarm

Form C contacts

 

 

 

When the rectifier is installed in an embedded shelf, the RC+, RG-, EQL (if equipped) and RFA monitoring signals are extended by the cable assembly which is fed through the rear of the shelf.

The connections available from the rectifier interface connector located at the rear of the unit are described in the “Rectifier and controller interface connections” section of this manual.

Refer to the reference section for all the interface signal wiring information for each shelf model number.

Following is a brief description of special interface or alarms signals for specific applications.

NT5C10BA-1/2, NT5C10BF-1 and NT5C10BP hot standby power shelf

The NT5C10BA-1/2, NT5C10BF-1 and NT5C10BP wiring is such that when the power shelf is equipped with two or more rectifiers, one rectifier is inhibited (Standby) and will be activated when one rectifier (Main or Regular) fails.

These power shelves are equipped with a relay that provides an alarm signal no standby rectifier (NSR) when the standby rectifier is missing from its position. Also two RFA signals are available for transmitting the alarm signal to the monitoring unit.

Note : The earlier vintage "Main" rectifier has been referred to as the "Regular" rectifier. See Appendix A for additional information on the NT5C10BF and NT5C10BP shelves.

UM5C06B / C ( 169-2071-500 ) P0711722 Standard 10.00 May 2001