Emerson MPR25 Procedure 10 - LVD installation in the shelf, Remove the LVD faceplate, Step

Models: MPR15 Series MPR25

1 120
Download 120 pages 55.76 Kb
Page 59
Image 59
LVD installation in the shelf

Installation and start-up procedures 59

LVD installation in the shelf

The LVD is installed in the right hand shelf position as describes in

Procedure 10.

Procedure 10 - LVD installation in the shelf

Step

Action

 

 

1

Release the clamping bar and blank panel (see Procedure 1).

 

 

2

Remove the LVD faceplate.

 

 

3

Slide the LVD about two thirds of the way into the shelf.

 

 

4

Connect the LVD as shown in Figure 22 and 23. (Use 2 X 10 AWG wires

 

for contactors).

 

 

5

Re-install the small LVD faceplate.

 

 

6

Push the LVD the remaining distance into the shelf and slide the blank

 

panel into the shelf between the LVD and the adjacent rectifier.

 

 

7

Secure the clamping bar by tightening the two captive screws.

 

 

 

end

 

 

Figure 22 - Embedded shelf - LVD connections - rear access

TO LOAD

CHASSIS

GROUND

[T]

BAT RTN

LOAD

BAT

[B]

8

2

1

BAT SENSE LEADS