Emerson MPR15 Series, MPR25 user manual Start-up procedure Factory set voltage limits

Models: MPR15 Series MPR25

1 120
Download 120 pages 55.76 Kb
Page 60
Image 60
Figure 23 - Embedded shelf - LVD connections - side access

60 Installation and start-up procedures

Figure 23 - Embedded shelf - LVD connections - side access

TO LOAD

[T]

BAT RTN

CHASSIS GROUND

Start-up procedureLOAD

Manual backgroundBAT

[B]

8

2

1

BAT SENSE LEADS

Start-up procedure

Factory set voltage limits

All rectifiers are factory set as follows unless otherwise requested by the customer:

 

MPR15

MPR25

Float Voltage:

52.10

V DC

48.00

V DC

Equalize:

0.70

V DC above float

0.00

V DC above float

HVSD:

59.00 V DC

56.50 V DC

LVD/LVD Alarms

 

 

 

Low Voltage Alarm (LVA):

47.00

V DC

Low Voltage Disconnect (LVD):

43.50

V DC

UM5C06B / C ( 169-2071-500 ) P0711722 Standard 10.00 May 2001

Page 60
Image 60
Emerson MPR15 Series, MPR25 Start-up procedure Factory set voltage limits, Embedded shelf - LVD connections - side access