General requirements

104 Appendix A: NT5C10BF-1 and NT5C10BP

General requirements

Power shelf size

The NT5C10BF-1 and NT5C10BP power shelves are designed specifically for the FTIP/FTOP application. They measure 17.0 inches W x 7.0 inches H x 12.0 inches D. They provide housing for up to three MPR25EX (NT5C06BB) SMRs (FTOP application), or two MPR15E (NT5C06CB/CD) SMRs plus one 50 A LVD module (NT6C13FA) (FTIP application). The middle rectifier is wired as Standby.

Shelf labeling

The following component and connection positions are labeled on the power shelf:

a)Front (left to right):

-MAIN1

-STANDBY

-MAIN2/LVD

b)Rear (right to left): Signal Connections:

- RC-

TB1-1

- RG+

TB1-2

- J1

TB1-3

- J2

TB1-4

- RFA

TB1-5

- NSR

TB1-6

Power Connections:

- RTNA

TB2-1

- -48V A

TB2-2

Note:

The Standby rectifier HVSD should be adjusted 0.5

 

higher than the main rectifier(s) and its float voltage

 

should be adjusted 0.1 volts lower than the main

 

rectifier(s).