Emerson MPR25 Maintenance Rectifier, Procedure 20 - Float/equalize and remote equalize, Step

Models: MPR15 Series MPR25

1 120
Download 120 pages 55.76 Kb
Page 73
Image 73
Maintenance

73

Maintenance

Maintenance

Rectifier

Procedure 20 - Float/equalize and remote equalize

Step

Action

 

 

1

Disconnect the sense leads from the rectifier, by either disconnecting a

 

quick disconnect tab TB1 on the shelf or removing the appropriate

 

system fuse. (See the “Introduction” chapter for system applications.)

2

Open the output DC breaker. The unit is ready for local adjustment.

 

 

3

The unit should provide voltage to the front panel test point terminals. If

 

it does not, cycle the AC breaker to reset the unit.

4

Momentarily hold the FLT/EQL switch to EQL for local equalize.

 

 

5

Using a voltmeter, verify and adjust the EQL potentiometer to obtain an

 

output voltage reading of 0.5 volts (see Note below) above the system

 

equalize requirement.

6

Release the FLT/EQL switch. Verify that the output voltage drops to the

 

float value plus 0.5V (see Note below).

7

Verify the HVSD level. It is recommended that it be set approximately 3 V

 

above the shutdown limit of the power system. Refer to the “Installation

 

and start-up procedure” chapter, subsection “Start-up procedure”, for the

 

verification procedure.

8

Reconnect the sense leads locally to the rectifier. Close the output DC

 

breaker. Cycle the AC breaker to reset the unit. The RFA/ON LED should

 

be green.

–end–

Note: The 0.5 volt DC extra does not apply to MPR25 rectifiers above Release 30.

25A Switch Mode RectifierNT5C06B / C Installation and User Manual

Page 73
Image 73
Emerson MPR25, MPR15 Series Maintenance Rectifier, Procedure 20 - Float/equalize and remote equalize, Step, Action