Emerson MPR15 Series Output voltage, Output noise and ripple, Floating, Equalizing, Current limit

Models: MPR15 Series MPR25

1 120
Download 120 pages 55.76 Kb
Page 18
Image 18
Output voltage

18 Specifications

Output voltage

Floating:

-46 V DC to -57 V DC

Equalizing:

0 to -2.5 V DC above float

Output regulation:

At the point of regulation: within +0.5% of the

 

selected value for all specified input and output

 

variations and within +1% for any combination of

 

specified input, output and environmental conditions.

Output protection:

30 A DC breaker

Output current:

at 96-132 V input * - 15 A for MPR15E/EX at 176-

 

264 V input – 25 A for MPR25E/EX

Current limit:

17.5 to 20 A minimum for 96-132 V input and 25.5 to

 

30 A for 176-264 V input. From -46 V DC to -57 V

 

DC. Constant power for output from -57 V DC to -

 

59.5 V DC

Note: The AC inrush current during the turn-on sequence of the rectifier, under all input and output conditions specified in this document, will not exceed its full load steady-state value.

Output noise and ripple

less than 22 dBrnC at voice frequency, with batteries measured at the point of regulation and over the entire range of the rectifier, inducing operation in the current limit mode, and low nominal and high input conditions.

less than 10 mVrms in any 3 kHz band between 10 kHz and 20 MHz. Measurements made with or without batteries at the output terminal of the rectifier and with the rectifier in the local sensing mode.

peak-to-peak switching voltage spikes less than 250 mV (600 mV from -40°C to 0° C), measured differentially with an oscilloscope at a 2 MHz bandwidth.

UM5C06B / C ( 169-2071-500 ) P0711722 Standard 10.00 May 2001