Fault diagnosis

 

 

Maintenance 79

Fault diagnosis

 

 

Symptom:

Possible cause

 

 

 

 

Low Voltage Test/Bypass

The switch is on the Test/Bypass position

 

LED lit

 

 

 

 

 

LVA and LVD LED lit

Check the voltage level at the test jacks and

 

 

the position of the Test switch. Verify the LVA

 

 

and LVD adjustment. Set the test switch to the

 

 

Test/Bypass position to verify their operation.

 

 

Replace the circuit pack if it is still not

 

 

operational.

 

The LVD disconnects the load

Verify the voltage at the test jacks. Remove the

 

 

faceplate and check the fuse located on the

 

 

control PCB.