Emerson MPR25 inch system shelf NT5C10CO, Procedure 2 - Common bussed AC connection - side access

Models: MPR15 Series MPR25

1 120
Download 120 pages 55.76 Kb
Page 47
Image 47
23-inch system shelf (NT5C10CO)

 

Installation and start-up procedures 47

23-inch system shelf (NT5C10CO)

Capacity:

- 1 x MPR15 + 1 x MPR15 “Delay Start”

AC common cable

- 2/12 AWG armored cable. Refer to Figure 13

 

(side)

DC cables

- 6 AWG (BAT and BAT RTN). Refer to Figure 18

 

(side) and to Figure 19 (rear)

Signals:

- 2 cables (for remote sensing and alarm)

Note :

See Appendix B for additional information.

Figure 13 - System shelf or embedded (left view) common bussed AC - side access

ATTENTIO

L2

CAUTION

L1

 

 

FR GRD

Procedure 2 - Common bussed AC connection - side access

Step

Action

1Punch out 1.125-inch dia. knockout on left side of shelf.

2Mount conduit connector with lock nut.

3Run and connect wires as illustrated.

4Re-install the blank panel to prevent access to the connections inside.

–end–

25A Switch Mode RectifierNT5C06B / C Installation and User Manual