Emerson MPR25, MPR15 Series user manual 25 A, 50 A, 75 A, V DC to -57 V DC, 15 A, 30 A, 45 A

Models: MPR15 Series MPR25

1 120
Download 120 pages 55.76 Kb
Page 39
Image 39
25 A

Operation 39

Output current:

one rectifier

25 A

 

two rectifiers

50 A

 

three rectifiers

75 A

Note that when three phase 208 / 240 V AC lines are used to power more than one shelf, it is preferable to distribute the shelves equally among the phases.

Use a 20 A breaker or FRN type fuse for individual AC.

Use a 40 A breaker or FRN type fuse for two rectifiers, common AC.

Use a 60 A breaker or FRN type fuse for three rectifiers, common AC.

When using the MPR15 rectifier powered from 120 V AC, the power shelf equipped with one, two, or three rectifiers has the following specifications:

Condition: Typical input current value for 54 V dc, full load output.( ) = maximum input current at Output 54 V dc, current limit minimum line

Input Voltage:

120 V AC

 

Frequency:

47-63 Hz

 

Range:

96-132 V AC

 

Input Current:

one rectifier

10.5 (16.5)

 

two rectifiers

21.0 (33.0)

 

three rectifiers

31.5 (49.5)

Use a 20 A breaker or FRN type fuse for individual AC.

Use a 40 A breaker or FRN type fuse for two rectifiers, common AC. Use a 60 A breaker or FRN type fuse for three rectifiers, common AC.

Output Voltage:

-46 V DC to -57 V DC

 

Output current:

one rectifier

15 A

 

two rectifiers

30 A

 

three rectifiers

45 A