Image 17
0° to +65° C (32° to 149° F) equipped without an air filter 0° to +50° C (32° to 122° F) equipped with an air filter
0 to 95% RH (non-condensing) Sea level to 2100 m (7000 ft.)

Specifications 17

Environmental specifications

Operating

CAUTION

An airflow clearance must be left at the rear of the shelf.

A minimum of three inches is recommended.

The rectifier will operate satisfactorily under the following environmental conditions:

Temperature Range: NT5C06DA/DB

Humidity:

Altitude:

Transportation

During transportation the rectifier can be subjected to the following conditions without sustaining damage:

Temperature Range:

-55° C (-67° F) for 16 hours

 

+70° C (158° F) dry heat

Humidity:

0 to 95% (non-condensing) 4 kPa max.

Vibration:

38mm/sec max. (10 to 30 Hz).

 

610 mm (24 inch) drop when packaged.

Pressure:

12 kPa min. (equiv. to 15 000 m altitude).

Temp. Shock:

-55° to 70°C (-67° to 158°F) (5 cycles)

Storage

For storage, the rectifier must not be kept in an environment exceeding:

Temperature Range:

-55°C (-67°F) +70°C (158°F) dry heat

Humidity:

0 to 95% (non-condensing) 4 kPa max.