6. Troubleshooting

Alarm indication

RFA fault

Table 9 - System fault diagnosis

Fault symptom

Possible causes

 

 

RFA

No AC input or input out of bounds.

 

 

 

No AC input or input out of bounds.

 

 

 

AC Input/DC output circuit breaker is open.

 

 

 

Rectifier has received a HVSD signal from the

 

controller.

 

 

 

An internal high voltage shutdown (HVSD) has

 

occurred. The internal High voltage shutdown point set too

 

low (below float or equalize setting).

 

 

 

Excessive impedance in one or both sense leads.

 

 

 

The cooling fan is failed.

 

 

 

DC circuit breaker is open.

 

 

 

A thermal shutdown has occurred.

 

Defective unit.

 

Excessive ambient air temperature.

 

Air inlet/outlet blocked, clogged air filter.

Helios Rectifier 25/48NT5C06D Installation and User Manual