Installation and start-up 21

Installing the AC power

Permanent AC connection to the MPS75 power shelf is done using two armored cable conductors, RW-90 or equivalent, as listed in Table 2. One must be routed to L1, and the other one to L2 and to the safety shelf frame ground (FR GND). The cabling must comply to the local electrical code. The power shelf is equipped with a strain relief to terminate the conduit. The cable length should be minimized and be properly secured.

Table 2 - AC cable wire size

 

 

2 RECTIFIER POSITIONS

 

3 RECTIFIER POSITIONS

Individual AC

12

AWG for each rectifier

12

AWG for each rectifier.

 

 

 

Common AC

8 AWG

6 AWG

 

 

 

 

 

Table 3 - AC Fuses

 

 

 

 

 

 

 

 

 

 

2 RECTIFIER POSITIONS

 

3 RECTIFIER POSITIONS

Individual AC

20

A max for each rectifier

20

A max for each rectifier

 

 

 

 

 

Common AC

40

A max.

60

A max.

 

 

 

 

 

Figure 4 - Power shelf common AC connection