24 Installation and start-up

Table 5 - Rectifier and Controller interface connections (8-pin connectors)

Pin #

Design.

Description

Signal

1

EQL

Remote Equalize

BAT RTN

2

RG+

Sensing Positive

BAT RTN

3

RC-

Sensing Negative

-48V

4

FAN ALM

Fan Failure

BAT RTN

5

HVSDR

Remote High Voltage Shutdown Reset

BAT RTN

6

HVSD

Remote High Voltage Shutdown

BAT RTN

7

RFA

Rectifier Failure Alarm

BAT RTN

8

TB

Temporary Release

BAT RTN

Note: Both RFA and Fan alarm relays are energized during normal operation and are de-energized during an alarm condition.

Table 6 - Rectifier and Controller interface connections (26-pin connector)

Pin #

Designation

Description

Signal

1

RC1 -

Sensing Negative rect (1)

BAT-

2

RFA1 (NC)

Rectifier (1) fail alarm

NC

3

TR1

Temporary Release Rect (1)

Bat RTN

4

SH1+

Shunt Positive Rect (1)

50 mV

5

SH1-

Shunt Negative Rect (1)

50 mV

6

RC2-

Sensing Negative Rect (2)

BAT-

7

RFA2 (NC)

Rectifier (2) fail alarm

NC

8

TR2

Temporary Release Rect (2)

Bat RTN

9

SH2+

Shunt Positive Rect (2)

50 mV

10

SH3-

Shunt Negative Rect (3)

50 mV

11

RC3-

Sensing Negative Rect (3)

BAT-

12

RFA3 (NC)

Rectifier (3) fail alarm

NC

13

TR3

Temporary Release Rect (3)

Bat RTN

14

SH3+

Shunt Positive Rect (3)

50 mV

15

SH3-

Shunt Negative Rect (3)

50 mV

16

CUR SHARE

Current Share

0 - 12VDC

17

RFA (C)

Rectifier Fail Alarm

Common

18

ALM COMMON

Alarms Common

Common

19

EQL

Remote Equalize

BAT RTN

20

RG+

Sensing Positive

BAT RTN

21

HVSDR

Remote High Voltage Shutdown Reset

BAT RTN

22

HVSD

Remote High Voltage Shutdown

BAT RTN

 

 

continued

 

UM5C06D ( 169-2071-504 ) P0831010 Standard 7.00 May 2001

Page 24
Image 24
Emerson NT5C06D user manual Remote Equalize, Sensing Positive, Sensing Negative, Fan Failure, Remote High Voltage Shutdown