Installation and start-up 29

Rectifier meter accuracy

The rectifier's current meter is precise within + 2%.

Start-up and verification

Repeat the following steps for each rectifier in turn.

Procedure 4 - Starting up the rectifier

Step

Action

1Close the AC circuit breaker in the AC service (main) panel.

2Connect an external meter to test points V- and V+ on the rectifier to be tested.

3Switch the AC circuit breaker of the rectifier. The voltmeter will indicate a float voltage.

Note: If the float voltage remains at 0 V DC, verify that the input voltage is within the specified range. If it stills remains at 0 V DC, refer to the troubleshooting section of this manual.

4Determine the system requirements for Float, Equalize and HVSD limits found in User Manual 167-7011-010. If the rectifier's factory set limits have to be changed, proceed as follows, otherwise proceed to step 13.

High Voltage Shutdown ( HVSD ) Adjustment :

5With the DC circuit breaker OFF, keep the AC breaker on and turn the HVSD potentiometer fully clockwise.

6Turn the FLT potentiometer slowly clockwise until the output voltage reaches the desired HVSD set point.

7Slowly turn the HVSD potentiometer counterclockwise until the rectifier shuts down and the float voltage starts to decay down to zero. Turn the Float potentiometer counterclockwise two turns and reset the rectifier by switching the AC circuit breaker OFF and then ON.

8Adjust the Float voltage to the correct level.

Float Voltage Adjustment :

9To adjust the float voltage use the FLT potentiometer. To increase the voltage turn the potentiometer clockwise, to decrease it turn it

counterclockwise .

continued

Helios Rectifier 25/48 Installation and User Manual

Page 29
Image 29
Emerson NT5C06D user manual Rectifier meter accuracy, Start-up and verification, Procedure 4 Starting up the rectifier Step