Installation and start-up 25

Table 6 - Rectifier and Controller interface connections (26-pin connector) ( continued )

Pin #

Designation

Description

Signal

23

DC BRK ALM

DC Circuit Breaker

NC

24

AC FAIL ALM

AC Line Fail Alarm

NC

25

SENSE FAIL

Sense Fail

NC

 

ALM

 

 

26

FAN ALM

Fan Alarm

NC

 

Note:

The normally closeed (NC) annotation signifies that the

 

 

alarm is sent when the contact between the alarm (NC)

 

 

and alarm common is closed (short-circuited). The alarm

RFA (C) and alarm common pins 17 and 18 are floating. These two alarm commons must be connected to the bat RTN at the system level for applications requiring non- floating alarm signals. The rect (1) indicates the rectifier in position (1) located on the right side of the MPS75 shelf.

In applications where no controller is available or desired, the current sharing functions among rectifiers in SLOPE or FORCE mode are still available. The signal cable remote sense connections RC- and RG+ must be connected to the desired remote sensing location ( batteries). In forced share mode, the forced share signal line of each shelf must be connected together in a daisy chain fashion. See Figures 7A and 7B for suggested methods of connecting the signal wire.

Helios Rectifier 25/48 Installation and User Manual

Page 25