Emerson NT5C06D SEN Fail fault, Erratic load fault, Current or voltage float fault, Float

Models: NT5C06D

1 56
Download 56 pages 21.78 Kb
Page 48
Image 48

48 Troubleshooting

SEN FAIL fault

Fault symptom

Possible causes

 

 

SEN FAIL

One or both remote sense leads is disconnected.

 

 

 

DC breaker is open.

 

 

 

Rectifier is still in walk-in.

 

Sense leads are reversed.

Erratic load fault

Fault symptom

Possible causes

 

 

Erratic load

Requirement exceeds total rectifier capacity.

 

 

Current or voltage float fault

Fault symptom

Possible causes

 

 

Current or voltage

With paralleled units, the float and/or equalize is

float

misadjusted causing one or more units to carry the load.

 

Unit is in 'equalize' mode and paralleled units are not.

 

 

 

Remote sense lead has excessive impedance or are not

 

connected on one or more rectifiers.

 

 

 

System batteries are in a recharge mode after AC

 

outage.

 

 

 

Current share mode selection is not the same for all

 

units.

 

 

 

Forced share line is disconnected. (in FS only)

 

 

UM5C06D ( 169-2071-504 ) P0831010 Standard 7.00 May 2001

Page 48