28 Installation and start-up

Verification

After completing the wiring of the power shelf perform the following:

Procedure 2 - Verification

Step

Action

1Verify that the power shelf has been mechanically secured.

2Verify that all the wiring performed is correct by using a voltmeter.

3Verify that all connections are mechanically correct (that is, tight, correct connector, correct marking etc.)

4Reinstall the AC and DC junction box cover on the left and right sides.

end-

Installing the rectifier

The NT5C06D rectifier is a plug-in unit intended for use in the MPS75 power shelf.

Procedure 3 - Rectifier installation procedure

Step

Action

1

Release the clamping bar by loosening the two captive screws

2

Remove the blank panel for the rectifier to be installed (place a finger in the

 

hole, lift up, pull forward, then lower to disengage upper tabs from the shelf

 

top). Store the panel at the bottom of the shelf, under the rectifier.

3

Ensure that both AC and DC circuit breakers are in the OFF position.

4

Use a voltmeter to verify that the AC supply at the input of the shelf is 208

 

/ 240 V AC nominal.

5

Carefully slide the rectifier in position on top of the stored blank panel.

6

Insure that the rectifier is firmly slid and seated into position.

7

Reinstall the clamping bar by securing the two captive screws.

end

Factory setting

The rectifier is factory set as indicated in Table 7.

Table 7 - Rectifier settings

 

Load

Slope load sharing method

 

Sharing

 

 

 

 

 

 

Rectifier Output Voltage (FLOAT)

54.5 V DC

± 0.1

V

Rectifier Output Voltage (EQUALIZE)

55.2 V DC

± 0.1 V

Rectifier High Voltage Shutdown (HVSD)

59.0 V DC

± 0.1

V

Rectifier Output Current Limit

30 A

± 0.5

A

UM5C06D ( 169-2071-504 ) P0831010 Standard 7.00 May 2001

Page 28