LOCATING YOUR

INSTALLATION

LOCATING YOUR

GAS FIREPLACE

1)When selecting a location for your fi replace, ensure that the clearances outlined on this page are met.

2)Provide adequate clearances for servicing.

3)The appliance must be installed on a fl at, solid, continuous surface (e.g. wood, metal, concrete). This may be the fl oor, or raised up on a platform to enhance its visual impact. If the appliance is going to be installed on carpeting, combustible linoleum tile or other combustible material other than wood flooring, the appliance must be installed on a metal or wood panel extending the full width and depth of the appliance.

4)The P95-3 Direct Vent Gas Fireplace can be installed in a recessed position or framed out into the room as in A, B, C, D. See Diagram 1.

A) Flat on Wall

B) Flat on Wall Corner

C) Recessed into

Wall/Alcove

D) Corner

Diagram 1

5)

This appliance is Listed for bedroom

 

installations when used with a Listed Millivolt

 

Thermostat. Some areas may have further

 

requirements, check local codes before

 

installation.

6)

The P95-3 Direct Vent Gas Fireplace is

 

approved for alcove installations, which

 

meet the clearances listed on this page.

MANUFACTURED

MOBILE HOME

ADDITIONAL

REQUIREMENTS

1)Ensure that structural members are not cut or weakened during installation.

2)Ensure proper grounding using the #8 ground lug provided. See the "Wiring Diagram" section.

OPTIONAL

HEATWAVE

DUCT SYSTEM KIT

#946-556

The HeatWave Air Duct Kit increases the effectiveness of your fi replace by dispersing warm air from the fireplace to remote locations in the same room or other rooms in your home.

Up to two kits may be installed on the fi replace. Please Note: Only 1 HeatWave kit may be operated at one time. This includes the internal blower option as well.

OPTIONAL

HEAT RELEASE KIT

#946-570

The Heat Release Kit expels warm air from the fi replace to the outside of the building, allowing the fi replace to be operated with less heat entering the room. The kit may be used on either the left or right side.

CLEARANCES

The clearances listed below are Minimum distances unless otherwise stated:

A major cause of chimney related fires is failure to maintain required clearances (air space) to combustible materials. It is of the greatest importance that this fireplace and vent system be installed only in accordance with these instructions.

Clearance to Combustibles from:

 

Back

0"

(0mm)

Side

0"

(0mm)

Floor

0"

(0mm)

NOTE: The minimum floor clearance must be maintained from the top surface of the carpeting, tile, etc.

Side Wall Clearance

6-1/2" (165mm)

Horizontal Vent Clearances

Top3"

Side2"

Bottom2"

Vertical Vent Clearances 1-1/4" (32mm)

*see mantle clearance instructions in the "Combustible Mantels" section.

7) Werecommendthatyouplanyourinstallation

on paper using exact measurements for

clearances and fl oor protection before

actually installing this appliance. Have a

qualified inspector, dealer, or installer review

your plans before installation.

Note: For vent terminations see the "Venting" section.

WARNING:

Fire hazard is an extreme risk if

these clearances are not adhered to.

Clearances for HeatWave and

Heat Release Kit

Heat Release Kit

The HeatWaveDuct Kit and the Heat Release Kit have different clearance and framing requirements, check the HeatWave and Heat Release manual for details.

Excalibur® P95-3 Zero Clearance Direct Vent Gas Fireplace