Excalibur electronic P95-LP3 Installation, Venting Arrangements - Horizontal Terminations

Models: P95-NG3 P95-LP3

1 44
Download 44 pages 25.34 Kb
Page 15
Image 15
VENTING ARRANGEMENTS - HORIZONTAL TERMINATIONS

INSTALLATION

VENTING ARRANGEMENTS - HORIZONTAL TERMINATIONS

SIMPSON DURA-VENT DIRECT VENT GS SYSTEM and

FPI DIRECT VENT SYSTEM (FLEX)

(Propane & Natural Gas)

The diagram shows all allowable combinations of vertical runs with horizontal terminations, using one 90o elbow (two 45o elbows equal one 90o elbow).

Simpson Dura-Vent 5" inner diameter 8" outer diameter

Note: Must use optional flue adapter (Part # 770-994) when using Simpson Dura-Vent pipe.

Regency® Flex Vent 5" inner diameter 8" outer diameter

Note: FPI Direct Vent System (Flex) is only approved for horizontal terminations.

A vent guard should be used whenever the termination is lower than the specifi ed minimum or as per local codes.

Please note that all vertical measurements are taken from the base of the unit excluding risers or bottom stand-offs.

Maintain clearances to combustibles as listed in the "Clearances," "Locating Your Gas Fireplace," "Combustible Mantels," "Unit Base Stand-offs," "Framing and Finishing," "Facing Requirement," & "Hearth Requirement" sections.

Horizontal vent must be supported every 3 feet.

Firestops are required at each floor level and whenever passing through a wall.

Excalibur® P95-3 Zero Clearance Direct Vent Gas Fireplace

15

Page 15
Image 15
Excalibur electronic P95-LP3 Installation, Venting Arrangements - Horizontal Terminations, Fpi Direct Vent System Flex