XXOUTPUT TYPE
DELETE0
Output Type
0 = delete
1 = relay on 4204/4229 module
2 = Powerline Carrier device
[∗] to continue
Select whether this is a relay or a Powerline Carrier
If Powerline Carrier is selected, go to “A” prompt. If relay is selected, skip to “B” prompt.
“A”
XX UNIT No.
yy
Unit Number
(prompt appears if
Enter the unit code (set at the device) and press [∗]. The system returns to the Output Number prompt.
“B”
XXMODULE ADDR
Module Address
(prompt appears if relay is selected)
Enter the predefined address for this module as listed below. Make sure the module’s DIP switches are set to the selected address.
Module Addresses
Address | Module |
07 | 1st 4229 (with zones |
08 | 2nd 4229 (with zones |
09† | 3rd 4229 (with zones |
10† | 4th 4229 (with zones |
11† | 5th 4229 (with zones |
12 | 1st 4204 |
13 | 2nd 4204 |
14† | 3rd 4204 |
15† | 4th 4204 |
† These addresses apply to FA168CPS only.
|
| Relay Position | This is the actual (or physical) relay number with respect to the | |
XX REL POSITION |
| |||
| Relay Module upon which it is located. For 4204 modules, relay | |||
zz | ||||
[∗] to continue | numbers are | |||
|
| |||
|
|
| The system returns to the Output Number prompt for | |
|
|
| programming the next device. |
∗80 OUTPUT FUNCTION MENU MODE
(press ∗80 while in Programming mode) The Output Definition Worksheet is on page Error! Bookmark not defined.. Use this mode to program output function definitions (up to 48 functions) that provide automated control of any of the output devices, based on events occurring on individual zones or zones with certain zone types. Each output definition is identified by an output function number, and includes the following components:
Output Definition Components
Component | Description |
Output Function No. | A reference number that defines an output’s characteristics. |
Activated By | Determines whether the initiating event occurs on a zone, a zone list, or a zone type. |
Event | Event that triggers the output action. Can be an event occurring on a specific zone number or a |
| zone list, or a specific zone type. |
Partition | If the output is activated by zone type, this defines the partition in which the programmed event is |
| to cause the device action. |
Output Action | Defines the action of the |
| seconds, stay closed until reset, continuously pulse |
| toggle the device state, or activate for a defined duration (set in data field *177). |
Output No. | Assigns this function to a specific output number (defined in *79 Menu Mode). This is the output |
| number that will perform this function upon the triggering event. Note that each defined function is |
| associated with only one output number. This means that if more than one output device needs to |
| perform this particular function, you need to define another output function number with the same |
| attributes, but assign the appropriate output number. (i.e. output devices can be assigned more |
| than one function number, but each function number can only be assigned a single output |
| number. |
For example, if you want to pulse a strobe light upon fire alarms on zone 4 using a relay mapped to output number 2 (as programmed in *79 Menu Mode), program the following in *80 Menu Mode:
Prompt |
| Entry | |
Output Funct. # | = | 01 | (assuming this is the first output function) |
Activated By: | = | 3 (zone number) | |
Enter Zn No. | = | 04 | (requires |
Output Action | = | 3 (continuous pulse) | |
Output Number | = | 02 | (device mapped in *79 Menu Mode) |
|
|