Programming Output Devices

OUTPUT DEVICE PROGRAMMING GENERAL INFORMATION (*79/*80 Menu Mode)

Output Devices: The FA168CPS system supports up to 16 relays and/or Powerline Carrier devices (X-10 devices) plus 2 built-in trigger outputs in any combination. These 18 “outputs” are assigned to system-wide output numbers (01-18). Use *79 Menu Mode to assign output numbers and map them to device addresses.

The FA148CP supports 8 relays and 2 built-in trigger outputs (total 10 outputs).

Output Functions: The system also provides installer-defined output functions, which can be assigned to any of the physical outputs. Therefore, the action of any one of the outputs can be based on as many of these defined functions as desired. This lets a single relay or X-10 device perform many functions.

The control supports: FA168CPS = up to 48 defined functions; FA148CP = up to 24 functions Use *80 Menu Mode to define output functions.

WARNING: Relays and output devices are not recommended for life safety applications.

NOTE: When navigating the *79 and *80 menus: The [] key is used to accept an entry and advance to the next prompt. The [#] key is used to revert back to the last question to check or change an entry. Press [] to go forward again.

Programming Output Devices

1.Use *79 Menu Mode to assign module and output numbers and map them to device addresses. NOTE: You must map output devices using *79 Menu Mode before you can use *80 menu Mode.

2.Use *80 Menu Mode to create output definitions, which control the output devices, if desired.

3.Use *81 Zone List Menu mode to define zone lists for use with output devices if the device action is based on more than one zone.

To program a device for manual activation (user code + [#] [7] / [#] [8] + 2-digit device number) or for scheduled automatic activation, simply map the device using *79 Menu mode.

To program a device to automatically activate upon a system event (or function key), use *79 Menu mode to map the device, then use *80 Menu mode to define the automated device action.

79 RELAY/POWERLINE CARRRIER DEVICE (X-10) PROGRAMMING MENU MODE

(press 79 while in Programming mode) The *79 Device Mapping Worksheet is on page Error! Bookmark not defined.. Use this menu to assign Relay Module device addresses and specific relay numbers, and Powerline Carrier unit numbers. The system is based on predefined module addresses for 4204 and 4229 modules. Refer to the table shown at the “Module Address” prompt on the next page and set the modules’ addresses (via module DIP switches) accordingly.

The following table shows how these outputs are identified.

Output Identification

 

This output…

is identified by…

 

Relays

the Relay Module’s device address and the relay position on that module (i.e. the physical relay

 

 

number, 1-4, on that module).

 

X-10 Device

a house ID (entered in data field *27) and the unit number of the device.

 

Built-in Outputs

the output number assigned, 17 for Trigger 1 and/or 18 for Trigger 2.

 

 

 

 

 

 

Device Output Number

This is the logical (or reference) relay number as used in the

 

ENTER OUTPUT NO.

 

FA168CPS:

system. Relays and X-10 devices are numbered 01-16; the on-

 

00 = QUIT

xx

 

01-16 = relays/X-10

board triggers are numbered 17 and 18 and can be programmed

 

 

 

 

 

 

17, 18 = on-board triggers

for inverted output, if required.

 

 

 

FA148CP:

 

 

 

 

01-08 = relays/X-10

 

 

 

 

17, 18 = on-board triggers

 

 

 

 

[] to continue

 

 

 

 

00 to quit

 

 

 

 

Output Normally Low

(prompt appears only for Triggers 17 and 18)

 

17 OUT NORM LOW

 

0 = no (standard default)

Selecting 0 (no) sets the output level normally high (default

 

0 = NO 1 = YES

0

 

1 = yes

setting).

 

 

 

 

 

 

[] to continue

Selecting 1 (yes) sets the output normally low.

Output Trigger 17 can be used for resetting 4-wire smoke detectors by connecting it to the negative power terminal of the smoke detector, selecting 1 at this prompt, and setting as zone type 54, fire zone reset, in *80 Menu mode.

After entry, display returns to Output Number prompt. Use *80 Menu mode to program the function of the trigger.

– 24 –

Page 24
Image 24
First Alert FA148CPSSIA manual Programming Output Devices, Output Identification, Device Output Number, Output Normally Low