Power Quality Logger
Safety Instructions
Table 4. 1744/1743 Power Quality Logger - Controls and Indicators
Item | Name | Description | |
|
|
| |
A | Power supply | Power supply voltage range: | |
leads and | |||
| |||
| Fixed installed voltage input cables for L1 or A, | ||
| neutral voltage | L2 or B, L3 or C, N. | |
| test leads | The highest permissible nominal voltage for power | |
|
| supply input is 660 V. | |
|
| The highest permissible nominal voltage for signal | |
|
| input is 830 V in a | |
|
| connection. | |
|
| In a | |
|
| highest permissible nominal voltage is 480 V. | |
|
| When using PTs and CTs for measuring voltage | |
|
| and current in a | |
|
| the IEC 60044 international standard for | |
|
| guidelines. | |
B | RS232 | The serial RS232 interface is used to communicate | |
interface port | with a PC. The Logger is connected to the PC’s | ||
| |||
|
| serial port (or a modem for remote communication) | |
|
| using the interface cable. Use a USB adapter if | |
|
| necessary. | |
C | START/STOP | The START/STOP button is used to start or end | |
| |||
|
| ||
D | Channel LEDs | The logging channel LEDs indicate whether the | |
| applied voltages and currents are within the | ||
|
| ||
|
| nominal range set using the PQ Log software. | |
|
| Continuously on = Logging signal in nominal range | |
|
| Short blinks = No or | |
|
| Long blinks = Overload | |
E | Power status | Continuously on = Power supply voltage in | |
LED | permissible range | ||
| |||
|
| Off = No power | |
F | Connector for | Flexi sets or current clamps are detected | |
Flexi Set or | automatically at | ||
| |||
| current clamps | probe type, be sure to remove and restore power so | |
|
| the Logger will detect the new current probe. | |
|
| Nominal ranges for the Flexi Set are 15 A, 150 A, | |
|
| 1500 A, and 3000 A ac. Nominal input for current | |
|
| clamps is 0.5 V. | |
G | Logging status | Continuously on = Logging in progress | |
LED | Blinking = Logging stopped or not started | ||
| |||
|
|
|
9