Power Quality Logger

Safety Instructions

Table 4. 1744/1743 Power Quality Logger - Controls and Indicators

Item

Name

Description

 

 

 

A

Power supply

Power supply voltage range: 88-660 V ac or

leads and

100-350 VDC, 50 Hz / 60 Hz, 600 V CAT III.

 

 

3-phase plus

Fixed installed voltage input cables for L1 or A,

 

neutral voltage

L2 or B, L3 or C, N.

 

test leads

The highest permissible nominal voltage for power

 

 

supply input is 660 V.

 

 

The highest permissible nominal voltage for signal

 

 

input is 830 V in a 3-wire network with Delta

 

 

connection.

 

 

In a 4-wire network with Wye connection, the

 

 

highest permissible nominal voltage is 480 V.

 

 

When using PTs and CTs for measuring voltage

 

 

and current in a medium-voltage network, refer to

 

 

the IEC 60044 international standard for

 

 

guidelines.

B

RS232

The serial RS232 interface is used to communicate

interface port

with a PC. The Logger is connected to the PC’s

 

 

 

serial port (or a modem for remote communication)

 

 

using the interface cable. Use a USB adapter if

 

 

necessary.

C

START/STOP

The START/STOP button is used to start or end

 

switch-operated logging sessions.

 

 

D

Channel LEDs

The logging channel LEDs indicate whether the

 

applied voltages and currents are within the

 

 

 

 

nominal range set using the PQ Log software.

 

 

Continuously on = Logging signal in nominal range

 

 

Short blinks = No or low-level signal

 

 

Long blinks = Overload

E

Power status

Continuously on = Power supply voltage in

LED

permissible range

 

 

 

Off = No power

F

Connector for

Flexi sets or current clamps are detected

Flexi Set or

automatically at power-up. If you change the current

 

 

current clamps

probe type, be sure to remove and restore power so

 

 

the Logger will detect the new current probe.

 

 

Nominal ranges for the Flexi Set are 15 A, 150 A,

 

 

1500 A, and 3000 A ac. Nominal input for current

 

 

clamps is 0.5 V.

G

Logging status

Continuously on = Logging in progress

LED

Blinking = Logging stopped or not started

 

 

 

 

9