Power Quality Logger
Technical Specifications
Power (Logging Functions A, P only) P, S, PActive power P | As per EN 61036, class 2 |
Distorting power D | As per EN 61268, class 2 |
Max value | Highest value per interval |
Min value | Smallest value per interval |
Phase uncertainty | < 0.3 degrees |
Conditions | Conductor centered within clamp jaws or |
| Flexi Set |
Voltage harmonics (function A) intrinsic uncertainty:
Current harmonics (function A) intrinsic uncertainty
THDV (function A) intrinsic uncertainty at VN
THDV (function P) intrinsic uncertainty at VN
THDI (functions A, P) intrinsic uncertainty at II
For Vm < 3% VN: < 0.15% VN
For Vm ≥ 3% VN: < 5% Vm
For Im < 10% IN: < 0.5% IN
For Im ≥ 10% IN: < 5% Im
For THDV < 3%: < 0.15%
For THDV ≥ 3%: < 5%
For THDV < 3%: < 1%
For THDV ≥3%: < 5%
For THDI < 3%: < 2%
For THDI ≥ 3%: < 5%
Frequency | 42 classes for 10 s mean values |
| |
Interharmonics | 21 classes for 3 s mean values |
53