Power Quality Logger
Logger Parameters with Function A
Logger Parameters with Function A
The following are the parameters of the 1744/1743 Logger with function A.
TRMS value of voltage and current. Basic values on 200 ms per phase.
RMS value of voltage and current per logging interval per phase
Active power calculated from FFT from samples of voltage and current.
Basic value on 200 ms per phase.
Fundamental
| 1 | N |
|
Vbas = | .∑V 2i | ||
| N | i=1 |
|
| 1 | N |
|
Ibas = | ⋅ ∑ Ii | 2 | |
| N | i=1 |
|
N: Number of samples in 200 ms intervals (2048)
V |
|
| 1 | M |
RMS | = | .∑V 2 | ||
|
| M | basj | |
|
|
| j=1 | |
|
|
| 1 | M |
I | RMS | = | ⋅ ∑ I 2 bas j | |
|
| M |
|
j=1
M:Number of 200 ms intervals per logging interval
Pn = Vn .In .cosϕ n
Vn: RMS value of voltage harmonics of order n
In: RMS value of current harmonics of order n
n: Order of the harmonics
φn: Phase angle between current and voltage harmonics of order n
Pn : Harmonics of the active power of order n
50
Pbas = ∑ Pn
n=1
Ph1bas = P1
41