1744/1743

Users Manual

1.Connect the voltage test leads to the outputs of the voltage transformers (VTs).

2.In PQ Log, select the measuring range with P-N logging and matching nominal voltage.

3.Enter the correct converter/transformer ratio for current and voltage.

Note

Current clamp sets are available for 1 A current transformers.

Logging with Two Voltage Converters and Two Current Transformers

In 3-phase 3-wire systems with two voltage converters (VTs) and two current transformers (CTs) in an Aron or Blondel measuring circuit, the Logger can measure only phase-phase (P-P, Delta).

L1

L2

L3

L3

L2, N

L1

1743 POWER LOGGER

 

START

R

STOP

I I I I V V V

2S

POWER

23

 

egb009.eps

Figure 10. Measuring 3-Phase Voltages in a 3-Wire System with Potential

Transformers (Aron Measuring Circuit)

24