1744/1743 Users Manual
General Specifications
RMS Logging Slow Voltage VariationsLogging values: Mean value | RMS values averaged over interval length |
Min, Max values | Averaging with selectable averaging time from |
| 0.5 periods to 5 s |
Max value | Max 10 ms RMS value per interval |
Min value: | Min 10 ms RMS value per interval |
Mean value | RMS values averaged over interval length |
Max value | Highest RMS value per interval |
Limit value | Variable |
| Lower limit: 0 to 95% VN |
| Upper limit: 105 to 120% VN |
| Set in PQ Log |
Range | 0 to VI + 20% |
Logging value | ½ period RMS value |
Operating uncertainty | < 2% of VI |
Response time | ½ line power period |
Flicker
Logging value | Flicker severity (Pst / Plt) according to |
| IEC |
Intrinsic uncertainty Pst | < 5% of m. v |
Measuring range Pst | 0.4 to 4 |
52