1744/1743

Users Manual

Time-activated job: The Logger starts logging as soon as the preprogrammed start time is reached, and stops at the defined end time.

Immediate job: The Logger starts logging as soon as power is on. Note the following about logging jobs:

The connection can be verified using the logging channel LEDs. If all three LEDs are lit continuously, the connection and the signal levels are within nominal range. For details, see Table 4 in the Features section.

The unit/job status is indicated by the status LED. For details, see Table 4 in the Features section.

Completing the Logging Job

1.Terminate the job as follows:

For switch-activated jobs: At the end of the logging period, stop the logging job by pressing the START/STOP button.

For time-activated and immediate jobs: Stop the job in PQ Log

with the icon, or with menu Logger/Stop logging.

Note

Make sure the logging job is stopped with the START/STOP button (switch-activated jobs) or PQ Log (time-activated jobs) before the test leads or power supply leads are removed. Otherwise, the Logger will record a voltage interruption.

Only switch-activated jobs can be aborted. Time-activated jobs are terminated only when the programmed measuring time has elapsed.

2.Remove the test leads of the three phases. Be sure to remove the measuring cable of the neutral wire last.

3.Remove the current probes.

26