Power Quality Logger

Methods of Logging

Voltage Interruptions

The Logger records two types of interruptions:

All measured RMS values of input voltages that are < 1% of the nominal voltage. (This threshold can be adjusted in PQ Log.)

Interruptions > 10 ms (0.5 line power periods).

The start time and duration of each interruption are registered.

110% Un

100% Un

90% Un

1%

Duration

Time

egb018.eps

Figure 15. Voltage Interruption

31