Power Quality Logger
Methods of Logging
Calculation of THD in Measuring Function PTHD – Measuring Function PFunction P does not measure harmonic values.
Voltages:THDV = VRMS 2 − V12
V1
VRMS: RMS value of total signal
V1: RMS value of the fundamental
Currents: THDI = I RMS 2 − I12
I1
IRMS: RMS value of the total signal.
I1: RMS value of the fundamental.
Note
THDI for currents < 5% of IE (measuring range) can have additional uncertainties, or can be suppressed.
Harmonics up to 50th order are taken into account.
Flicker
Flicker is the visual impression of unsteadiness in a light source whose luminance or spectral distribution changes over time. Flicker is logged in accordance with the IEC
35