| Power Quality Logger |
| Technical Specifications |
|
|
Power Supply |
|
Functional range | 88 to 660 V RMS ac absolute, 50 Hz / 60 Hz |
Safety | EN |
| pollution degree 2, double insulation |
Fuse | Power supply fuse can be replaced only in service |
| facility. Supply can be connected in parallel to |
| measuring inputs (up to 660 V RMS ac). |
Power consumption | 5 W |
Memory capacity | 8 MB |
Intervals | > 5.600 intervals, > 39 days with |
Events | > 13.000 |
Memory model | Linear, circular |
Interface | RS232, 9600 to 115000 Baud, automatic selection, |
| |
Dimensions | 170 mm x 125 mm x 55 mm |
Weight | Approx. 0.9 kg |
Measurement |
|
A/D converter | 16 bit |
Sampling frequency | 10.24 kHz |
Frequency response | Uncertainty < 1% of Vm for 40 to 2500 Hz |
Interval length | 1, 3, 5, 10, or 30 seconds, |
| 1, 5, 10, 15, or 60 minutes |
Averaging time for | ½ , 1 line power period |
min/max values | 200 ms |
| 1, 3, 5 s |
Time base | Resolution: 10 ms (at 50 Hz) deviation: 2 s/day |
| at 23 °C. |
49