GE 994-0089 user manual » To connect the System Fail relay, Power Fail Alarm Connection

Models: 994-0089

1 92
Download 92 pages 54.5 Kb
Page 70
Image 70

GE Energy

Power Fail Alarm Connection

Station Battery / Power Source

Light ON when

Light ON after

operational

failure

System Fail

The D400 includes a System Fail contact closure to provide an external LED indication on the system or LAN status.

The LED notification can be wired to operate as follows:

ON when system is functioning properly

ON when system failure has occurred

The System Fail contact closure provides three contacts (terminals 4, 5 and 6) on terminal block TB2.

!Caution: Contact closure rated for 0.1 A @ 300 V maximum.

»To connect the System Fail relay:

1.Remove the terminal block protective plastic cover.

2.Wire a lamp to terminals 4, 5 and 6 on terminal block TB2 as follows:

To enable the indicator when power is…

Wire the lamp between…

 

 

Functioning properly

Terminals 4 and 5

 

 

Failed

Terminals 5 and 6

 

 

For proper connection, the recommended tool torque settings for power terminal screws are 10.8 in-lb [1.22 Nm].

3.Replace the terminal block protective plastic cover.

70994-0089–1.00–2, General

Page 70
Image 70