GE Energy

DTE (default)

A

B

1

2

3

4

5

DCE

A

B

1

2

3

4

5

Switch SW3/SW4 Configuration

Switches SW3 (for Port 2) and SW4 (for Port 1) control the signals on Pins 4 and 6 of the RS-232 port. Each switch contains four switch positions that can each be set to ON or OFF to select the appropriate function for the port option. See illustrations below showing the switch positions for each setting.

RS-232 Card Switch SW3/SW4 Settings

Function

Pin 6

SW3/SW4 Positions

Pin 4

SW3/SW4 Positions

Signal

 

 

 

 

Signal

 

 

 

 

1

2

3

4

5

6

7

8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DTE (default)

DSR Input

OFF

OFF

ON

OFF

DTR

OFF

ON

OFF

OFF

 

Output

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DCE

DTR

OFF

ON

OFF

OFF

DSR Input

OFF

OFF

ON

OFF

 

Output

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

IRIG-B

Ground

OFF

OFF

OFF

ON

IRIG-B

ON

OFF

OFF

OFF

Enable

Output

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

D400 Substation Data Manager User's Manual 29

Page 29
Image 29
GE 994-0089 user manual Switch SW3/SW4 Configuration, DTE default