GE 994-0089 user manual See .5 Fiber Optic Serial Adapter for configuration options

Models: 994-0089

1 92
Download 92 pages 54.5 Kb
Page 54
Image 54

GE Energy

Warning: LED transmitters are classified as IEC 60825-1 Accessible Emission Limit (AEL) Class 1M. Class 1M devices are considered eye safe to the unaided eye. Do not view directly with optical instruments.

See section “3.5 Fiber Optic Serial Adapter” for configuration options.

»To connect fiber optic links to the Fiber Optic adapters, plug fiber optic cables into the corresponding TX and RX connectors.

Hot Standby Fiber Optic Connections

The Hot Standby Fiber Optic Ethernet Switch (GE Part No. 520-0214) is a 100BaseSX (820- 850 nm) network switch that supports single-IP redundancy for the D400. It provides automated fail over between two Ethernet fiber optic network connections (RX1/TX1 and RX2/TX2) that share a single MAC address.

The Hot Standby Fiber Optic Ethernet Switch can be installed in the NET1 or NET2 slot (slots 11 and 12) on the D400.

If two Hot Standby Ethernet switches are installed in the NET slots, the system may be used in a dual-IP redundancy mode. That is, each switch can be configured with a different IP address to provide a back up network connection if the primary channel fails.

You can use the following glass optical fiber (GOF) cabling with the D400 Glass Optical Fiber Serial adapter:

50/125 µm core/cladding multi-mode (gradient index) cable

62.5/125 µm core cladding multi-mode (gradient index) cable

100/140 µm core/cladding multi-mode (gradient index) cable

200 µm core Hard-Clad Silica (HCS) multi-mode (step index) cable

You can use the following fiber optic terminations for D400 cabling:

ST Connectors

When calculating cable length, consider the following optical power levels:

Glass optical fiber transmitter power is –19.0 ± 2 dBm

Glass optical fiber receiver sensitivity is typically –31.0 dBm

Warning: LED transmitters are classified as IEC 60825-1 Accessible Emission Limit (AEL) Class 1M. Class 1M devices are considered eye safe to the unaided eye. Do not view directly with optical instruments.

54994-0089–1.00–2, General