GE Energy

Environmental

Operating temperature

-20 °C to +65 °C

 

Maximum ambient temperature is +50 °C for unit to fully

 

comply with IEC 61010-1 Section 10.1 regarding surface

 

temperature limits for protection against burns.

 

 

Humidity rating

5 % to 95 % relative humidity, non-condensing

 

 

Environmental rating

Ingress protection: IP30 (IEC 60529)

 

 

Installation / overvoltage

CAT III

category

 

 

 

Pollution degree

2

 

 

Use

Indoor use only

 

 

Altitude

Maximum altitude 10,000 ft [3000 m]

 

 

Software

Firmware

Embedded application dependent

 

 

Human machine interface

Built-in graphical user interface (Web browser-based)

 

 

Configuration

Built-in graphical user interface (Web browser-based)

 

Offline Configuration Manager (PC-based) - Future

 

 

Soft logic

IEC 61131-3 soft logic engine - Future

 

LogicLinx* Editor (if using LogicLinx)

 

 

1.5Storage Recommendations

Storage Conditions

Always store the D400 in an environment compatible with operating conditions. Recommended environmental conditions for storage are:

Temperature: -40 °C to +90 °C

Relative humidity: 5 % to 95 %, non-condensing

Exposure to excessive temperature or other extreme environmental conditions might cause damage and/or unreliable operation.

Battery Life

To maintain the life of the battery, you should remove the battery if the D400 will be powered down or stored for more than six months.

See section “7.2 Replacing the Battery”.

18994-0089–1.00–2, General