GE Energy

Switch SW3/SW4 Configuration

Switches SW3 (for Channel 2 on TB1-6 through TB1-10) and SW4 (for Channel 1 on TB1-1 through TB1-5) contain ten DIP-switches that control pull-up and pull-down resistors for the differential data lines and provide line termination between the differential data pairs. Each DIP-switch can be set to ON or OFF to select the appropriate function for the switch. That is, if all pins are set to ON, switch is ON. If all pins are set to OFF, switch is OFF.

If termination/pull up is selected, the TX+ and RX+ signals have a 680 ohm pull-up resistor, the TX- and RX- signals have a 680 ohm pull-down resistor, and the RX and TX signals have a 120 ohm termination.

RS-485 Card Switch SW3/SW4 Settings

SW3/SW4 Pin

Pin Position

 

Function

 

 

 

 

1

ON

 

Pull-up for TX+

 

 

 

OFF

 

No pull-up for TX+

 

 

 

 

 

 

2

ON

 

Pull-down for TX-

 

 

 

OFF

 

No pull-down for TX-

 

 

 

 

 

 

3

Not connected

 

 

 

 

 

4

ON

 

Pull-up for RX+

 

 

 

OFF

 

No pull-up for RX+

 

 

 

 

 

 

5

ON

 

Pull-down for RX-

 

 

 

OFF

 

No pull-down for RX-

 

 

 

 

 

 

6

ON

 

Line termination between TX+ and TX-

 

 

 

OFF

 

No Line termination between TX+ and TX-

 

 

 

 

 

 

7

ON

 

Line termination between TX+ and TX-

 

 

 

OFF

 

No Line termination between TX+ and TX-

 

 

 

 

 

 

8

Not connected

 

 

 

 

 

9

ON

 

Line termination between RX+ and RX-

 

 

 

OFF

 

No Line termination between RX+ and RX-

 

 

 

 

 

 

10

ON

 

Line termination between RX+ and RX-

 

 

 

OFF

 

No Line termination between RX+ and RX-

 

 

 

 

 

 