Goodmans GPC1324H41A, GPC 13 SEER R-410A PACKAGE COOLING SPECIFICATIONS GPC1324-30H41AA

Models: GPC1324H41A GPC 13 SEER R-410A

1 47
Download 47 pages 14.36 Kb
Page 11
Image 11
PACKAGE COOLING SPECIFICATIONS GPC13[24-30]H41AA

PACKAGE COOLING SPECIFICATIONS GPC13[24-30]H41AA

 

 

GPC1324H41*

GPC1330H41*

 

 

 

 

COOLING

COOLING CAPACITY, BTUH

24,000

28,600

CAPACITY

SEER

13.0

13.0

 

 

 

 

UNIT

VOLTAGE (NAMEPLATE)

208-230/1/60

208-230/1/60

ELECTRICAL

AMPS (TOTAL)

10.5

13.16

SPECIFICATION

MINIMUM CIRCUIT AMPACITY

12.5

15.6

 

MAXIMUM OVERCURRENT PROTECTION (1)

20

25

COMPRESSOR

TYPE

RECIP

RECIP

 

RATED LOAD AMPS

7.9

9.8

 

LOCKED ROTOR AMPS

41

55

 

 

 

 

CONDENSER

HORSEPOWER

1/6

1/4

FAN MOTOR

RPM

815

830

 

FULL LOAD AMPS

1.1

1.5

 

LOCKED ROTOR AMPS

1.7

3.0

 

 

 

 

CONDENSER FAN

BLADE DIAMETER (INCHES) / # OF BLADES

22 / 3

22 / 3

 

 

 

 

CONDENSER

FACE AREA - SQ. FT.

13.4

13.4

COIL

NUMBER OF ROWS

1

1

 

FINS PER INCH

24

24

 

 

 

 

EVAPORATOR

HORSEPOWER - NO. OF SPEEDS

1/4 - 3

1/3 - 3

BLOWER

FULL LOAD AMPS

1.5

1.86

MOTOR

LOCKED ROTOR AMPS

2.2

3.2

 

MOTOR SPEED TAP - COOLING

MEDIUM

LOW

 

RPM

1075

1075

 

 

 

 

EVAPORATOR

DIAMETER X WIDTH (INCHES)

9 x 6

9 x 6

BLOWER

RATED SCFM COOLING

815

1,080

 

MAX EXTERNAL STATIC PRESS ("w.c.)

0.5

0.5

 

 

 

 

EVAPORATOR

FACE AREA - SQ. FT.

4.6

4.6

COIL

NUMBER OF ROWS

3

3

 

FINS PER INCH

14

14

 

 

 

 

GENERAL

FILTER SIZE - SQ. FT. *

20 x 20 x 1

20 x 25 x 1

INFORMATION

DRAIN SIZE (INCHES)

3/4"

3/4"

 

EXPANSION DEVICE

ORIFICE (0.059)

ORRIFICE (0.060)

 

REFRIGERANT CHARGE R-410A (Oz.)

80

80

 

POWER SUPPLY CONDUIT KNOCKOUT SIZE (IN

3/4, 1, 1-1/4

3/4, 1, 1-1/4

 

LOW VOLTAGE CONDUIT KNOCKOUT SIZE (IN.)

1/2

1/2

 

SHIPPING WEIGHT LBS.

310

310

 

OPERATING WEIGHT LBS.

300

300

 

 

 

 

(1)Maximum Overcurrent Protection Device: MUST use Time Delay Fuse or HACR type Circuit Breaker of the same size as noted. * Calculated external filter size based on air velocity of 300 ft/min.

Wire size should be determined in accordance with National Electrical Codes. Extensive wire runs will require larger wire sizes.

Unit specifications are subject to change without notice. ALWAYS refer to the units serial plate for the most up-to-date general and electrical information.

IMPORTANT: While this data is presented as a guide, it is important to electrically connect the unit and properly size wires and fuses/circuit breakers in accordance with the National Electrical Code and/or all local codes. Data shown is w/o electric heaters.

11

Page 11
Image 11
Goodmans GPC1324H41A, GPC 13 SEER R-410A service manual PACKAGE COOLING SPECIFICATIONS GPC1324-30H41AA

FAQ

What is the SEER rating for Goodmans GPC 13 SEER R-410A models GPC1324H41A and GPC1330H41A?

The SEER rating for both models is 13.0.

What is the maximum external static pressure for the condenser fan of Goodmans GPC 13 SEER R-410A model GPC1324H41A?

The maximum external static pressure for the condenser fan is 0.5" w.c.

What type of expansion device is used in Goodmans GPC 13 SEER R-410A models GPC1324H41A and GPC1330H41A?

Both models use orifice type expansion devices with specific orifice sizes mentioned for each model.