Goodmans COOLING PERFORMANCE DATA 5MM COILS GPC1324H41AB, Expanded Performance Data

Models: GPC1324H41A GPC 13 SEER R-410A

1 47
Download 47 pages 14.36 Kb
Page 33
Image 33
MODEL: GPC1324H41A*

 

MODEL: GPC1324H41A*

 

 

 

 

 

EXPANDED PERFORMANCE DATA

 

 

 

COOLING OPERATION

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Outdoor Ambient Temperature

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

65

 

 

75

 

 

 

 

85

 

 

 

95

 

 

105

 

 

115

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Entering Indoor Wet

Bulb Temperature

 

 

 

 

 

 

 

 

 

 

IDB*

Airflow

 

59

 

63

 

67

71

59

63

 

67

71

59

63

 

67

71

59

63

 

67

71

59

63

67

71

59

63

67

71

 

 

 

MBh

23.2

 

24.0

 

26.3

-

22.6

23.5

 

25.7

-

22.1

22.9

 

25.1

-

21.6

22.3

 

24.5

-

20.5

21.2

23.3

-

19.0

19.7

21.5

-

 

 

 

S/T

1.00

 

1.00

1.00

-

1.00

1.00

 

1.00

-

1.00

1.00

1.00

-

1.00

1.00

1.00

-

1.00

1.00

1.00

-

1.00

1.00

1.00

-

 

 

 

Delta T

22

 

23

25

-

22

23

 

25

-

21

22

24

-

21

22

24

-

20

21

23

-

18

19

21

-

 

 

950

KW

1.63

 

1.67

1.72

-

1.75

1.79

 

1.84

-

1.86

1.90

1.96

-

1.95

1.99

2.06

-

2.03

2.07

2.14

-

2.10

2.14

2.21

-

 

 

 

AMPS

7.1

 

7.2

7.4

-

7.6

7.7

 

7.9

-

8.1

8.3

8.5

-

8.6

8.8

9.0

-

9.0

9.2

9.5

-

9.5

9.7

10.0

-

 

 

 

HI PR

217

 

234

247

-

244

263

 

277

-

278

299

315

-

316

340

359

-

356

383

404

-

393

423

447

-

 

 

 

LO PR

110

 

117

127

-

116

123

 

135

-

121

128

140

-

127

135

147

-

133

141

154

-

137

146

159

-

 

 

 

MBh

22.8

 

23.7

25.9

-

22.3

23.1

 

25.3

-

21.8

22.6

24.7

-

21.2

22.0

24.1

-

20.2

20.9

22.9

-

18.7

19.4

21.2

-

 

 

 

S/T

1.00

 

1.00

1.00

-

1.00

1.00

 

1.00

-

1.00

1.00

1.00

-

1.00

1.00

1.00

-

1.00

1.00

1.00

-

1.00

1.00

1.00

-

 

 

 

Delta T

25

 

26

28

-

24

25

 

27

-

24

24

27

-

23

24

26

-

22

23

25

-

20

21

23

-

 

70

850

KW

1.63

 

1.66

1.71

-

1.74

1.78

 

1.83

-

1.85

1.89

1.95

-

1.94

1.98

2.04

-

2.02

2.06

2.13

-

2.09

2.13

2.20

-

 

 

 

AMPS

7.0

 

7.2

7.4

-

7.5

7.7

 

7.9

-

8.1

8.2

8.5

-

8.5

8.7

9.0

-

9.0

9.2

9.5

-

9.5

9.7

9.9

-

 

 

 

HI PR

216

 

232

245

-

242

261

 

275

-

276

297

313

-

314

338

357

-

353

380

401

-

390

420

443

-

 

 

 

LO PR

109

 

116

127

-

115

123

 

134

-

120

127

139

-

126

134

146

-

132

140

153

-

136

145

158

-

 

 

 

MBh

21.7

 

22.5

24.6

-

21.2

22.0

 

24.1

-

20.7

21.4

23.5

-

20.2

20.9

22.9

-

19.2

19.9

21.8

-

17.8

18.4

20.2

-

 

 

 

S/T

1.00

 

1.00

1.00

-

1.00

1.00

 

1.00

-

1.00

1.00

1.00

-

1.00

1.00

1.00

-

1.00

1.00

1.00

-

1.00

1.00

1.00

-

 

 

750

Delta T

27

 

28

30

-

26

27

 

29

-

25

26

29

-

25

26

28

-

23

24

27

-

22

23

25

-

 

 

KW

1.60

 

1.63

1.68

-

1.72

1.75

 

1.81

-

1.82

1.86

1.92

-

1.91

1.95

2.01

-

1.99

2.03

2.09

-

2.05

2.10

2.16

-

 

 

 

AMPS

6.9

 

7.1

7.3

-

7.4

7.6

 

7.8

-

7.9

8.1

8.3

-

8.4

8.6

8.8

-

8.9

9.0

9.3

-

9.3

9.5

9.8

-

 

 

 

HI PR

212

 

228

241

-

237

256

 

270

-

270

291

307

-

308

331

350

-

346

372

393

-

382

412

435

-

 

 

 

LO PR

107

 

114

124

-

113

120

 

131

-

117

125

136

-

123

131

143

-

129

137

150

-

134

142

155

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MBh

23.6

 

24.3

26.3

28.2

23.0

23.7

 

25.7

27.5

22.5

23.1

25.0

26.9

21.9

22.6

24.4

26.2

20.8

21.4

23.2

24.9

19.3

19.9

21.5

23.1

 

 

 

S/T

1.00

 

1.00

1.00

1.00

1.00

1.00

 

1.00

1.00

1.00

1.00

1.00

1.00

1.00

1.00

1.00

1.00

1.00

1.00

1.00

1.00

1.00

1.00

1.00

1.00

 

 

950

Delta T

23

 

23

25

27

22

23

 

25

27

22

22

24

26

21

22

24

25

20

21

22

24

19

19

21

22

 

 

KW

1.65

 

1.68

1.73

1.78

1.77

1.80

 

1.86

1.92

1.87

1.91

1.97

2.04

1.97

2.01

2.07

2.14

2.05

2.09

2.16

2.23

2.12

2.16

2.23

2.30

 

 

 

AMPS

7.1

 

7.3

7.5

7.7

7.6

7.8

 

8.0

8.2

8.2

8.3

8.6

8.8

8.6

8.8

9.1

9.4

9.1

9.3

9.6

9.9

9.6

9.8

10.1

10.4

 

 

 

HI PR

220

 

236

250

260

247

265

 

280

292

280

302

319

332

319

344

363

378

359

387

408

426

397

427

451

470

 

 

 

LO PR

111

 

118

129

137

117

125

 

136

145

122

130

141

151

128

136

149

158

134

143

156

166

139

147

161

171

 

 

 

MBh

23.2

 

23.9

25.9

27.8

22.7

23.4

 

25.3

27.1

22.1

22.8

24.7

26.5

21.6

22.2

 

24.1

25.8

20.5

21.1

22.9

24.5

19.0

19.6

21.2

22.7

 

 

 

S/T

1.00

 

1.00

1.00

1.00

1.00

1.00

 

1.00

1.00

1.00

1.00

1.00

1.00

1.00

1.00

 

1.00

1.00

1.00

1.00

1.00

1.00

1.00

1.00

1.00

1.00

 

 

 

Delta T

25

 

26

28

30

25

25

 

27

29

24

25

27

29

23

24

 

26

28

22

23

25

27

21

21

23

25

 

75

850

KW

1.64

 

1.67

1.72

1.77

1.76

1.79

 

1.85

1.91

1.86

1.90

1.96

2.02

1.96

2.00

 

2.06

2.13

2.04

2.08

2.15

2.22

2.10

2.15

2.22

2.29

 

 

 

AMPS

7.1

 

7.2

7.4

7.7

7.6

7.7

 

7.9

8.2

8.1

8.3

8.5

8.8

8.6

8.8

 

9.0

9.3

9.1

9.3

9.5

9.8

9.5

9.7

10.0

10.4

 

 

 

HI PR

218

 

235

248

259

245

263

 

278

290

278

300

316

330

317

341

 

360

376

357

384

405

423

394

424

448

467

 

 

 

LO PR

110

 

117

128

136

116

124

 

135

144

121

129

140

150

127

135

 

148

157

133

142

155

165

138

146

160

170

 

 

 

MBh

22.1

 

22.7

24.6

26.4

21.5

22.2

 

24.0

25.8

21.0

21.7

23.4

25.2

20.5

21.1

 

22.9

24.5

19.5

20.1

21.7

23.3

18.1

18.6

20.1

21.6

 

 

 

S/T

1.00

 

1.00

1.00

1.00

1.00

1.00

 

1.00

1.00

1.00

1.00

1.00

1.00

1.00

1.00

1.00

1.00

1.00

1.00

1.00

1.00

1.00

1.00

1.00

1.00

 

 

750

Delta T

27

 

28

30

32

26

27

 

29

32

26

27

29

31

25

26

28

30

24

25

27

29

22

23

25

26

 

 

KW

1.61

 

1.65

1.69

1.75

1.73

1.77

 

1.82

1.88

1.83

1.87

1.93

1.99

1.93

1.97

2.03

2.09

2.00

2.05

2.11

2.18

2.07

2.11

2.18

2.25

 

 

 

AMPS

7.0

 

7.1

7.3

7.6

7.5

7.6

 

7.8

8.1

8.0

8.2

8.4

8.7

8.5

8.6

8.9

9.2

8.9

9.1

9.4

9.7

9.4

9.6

9.9

10.2

 

 

 

HI PR

214

 

230

243

253

240

258

 

273

284

273

294

310

323

311

334

353

368

350

376

397

414

386

416

439

458

 

 

 

LO PR

108

 

115

125

133

114

121

 

132

141

118

126

138

147

124

132

145

154

130

139

151

161

135

144

157

167

33

 

* IDB: Entering Indoor Dry Bulb Temperature

 

 

 

NOTE: Shaded area is ACCA (TVA) conditions

 

 

 

 

 

 

 

 

 

 

 

 

High and low pressures are measured at the liquid and suction access fittings.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

COOLING PERFORMANCE DATA 5MM COILS GPC1324H41AB

Page 33
Image 33
Goodmans service manual COOLING PERFORMANCE DATA 5MM COILS GPC1324H41AB, Expanded Performance Data, MODEL: GPC1324H41A

FAQ

What is the model of the Goodmans air conditioner for the provided data?

The cooling performance data is for the GPC1324H41A model.

What measurements are included in the cooling performance data?

The data includes outdoor temperature, airflow, Delta T, KW, AMPS, and high and low pressure measurements.

How can I use the provided data to assess the cooling performance of the air conditioner?

The data can be used to understand the efficiency and effectiveness of the GPC1324H41A air conditioner under various conditions.