Goodmans GPC1324H41A COOLING PERFORMANCE DATA GPC1360H41BA, Expanded Performance Data

Models: GPC1324H41A GPC 13 SEER R-410A

1 47
Download 47 pages 14.36 Kb
Page 25
Image 25
Manual background

25

MODEL: GPC1360H41**

EXPANDED PERFORMANCE DATA

COOLING OPERATION

Design Subcooling, 12±3 °F @ the liquid access fitting connection AHRI 95 test conditions. Design Superheat 8±3 °F @ the compressor suction access fitting connection.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Outdoor Ambient Temperature

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

65

 

 

 

75

 

 

 

85

 

 

95

 

 

 

105

 

 

115

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Entering Indoor Wet

Bulb Temperature

 

 

 

 

 

 

 

 

 

 

 

IDB*

 

Airflow

 

59

63

 

67

71

59

63

 

67

71

59

63

 

67

71

59

63

 

67

71

59

63

67

71

59

63

67

71

 

 

 

 

MBh

58.3

59.6

 

63.7

68.1

57.0

58.2

 

62.2

66.5

55.6

56.8

 

60.7

64.9

54.3

55.4

 

59.2

63.3

51.5

52.7

56.3

60.1

47.7

48.8

52.1

55.7

 

 

 

 

S/T

0.94

0.88

0.71

0.53

0.97

0.91

0.74

0.55

1.00

0.93

0.76

0.57

1.00

0.96

 

0.78

0.59

1.00

1.00

0.81

0.61

1.00

1.00

0.82

0.61

 

 

 

 

Delta T

24

23

20

16

24

23

20

16

25

23

20

16

24

24

 

20

16

23

23

20

16

21

22

19

15

 

 

 

2085

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

KW

4.05

4.14

4.27

4.41

4.36

4.46

4.60

4.75

4.64

4.74

4.90

5.06

4.88

4.99

 

5.16

5.33

5.09

5.21

5.38

5.56

5.27

5.39

5.57

5.76

 

 

 

 

AMPS

19.1

19.5

20.0

20.6

20.3

20.7

21.3

21.9

21.8

22.2

22.8

23.5

23.0

23.5

 

24.1

24.9

24.2

24.7

25.4

26.2

25.4

26.0

26.7

27.6

 

 

 

 

HI PR

238

256

270

282

267

287

303

316

303

326

345

359

345

372

 

393

409

389

418

442

461

429

462

488

509

 

 

 

 

LO PR

112

119

130

138

118

125

137

146

122

130

142

152

129

137

 

149

159

135

143

157

167

139

148

162

173

 

 

 

 

MBh

56.6

57.9

61.8

66.1

55.3

56.5

60.4

64.5

54.0

55.2

58.9

63.0

52.7

53.8

 

57.5

61.5

50.0

51.1

54.6

58.4

46.3

47.4

50.6

54.1

 

 

 

 

S/T

0.89

0.84

0.68

0.51

0.92

0.87

0.71

0.53

0.95

0.89

0.72

0.54

0.98

0.92

 

0.75

0.56

1.00

0.95

0.78

0.58

1.00

0.96

0.78

0.58

 

80

 

1850

Delta T

25

24

21

17

25

24

21

17

25

24

21

17

26

25

 

21

17

25

24

21

17

23

23

20

16

 

 

KW

4.02

4.10

4.23

4.37

4.33

4.42

4.57

4.72

4.60

4.70

4.86

5.02

4.84

4.95

 

5.12

5.29

5.05

5.16

5.33

5.51

5.23

5.34

5.52

5.71

 

 

 

 

AMPS

19.0

19.3

19.8

20.4

20.2

20.6

21.1

21.8

21.6

22.0

22.6

23.3

22.8

23.3

 

23.9

24.7

24.0

24.5

25.2

26.0

25.2

25.8

26.5

27.4

 

 

 

 

HI PR

235

253

267

279

264

284

300

313

300

323

341

356

342

368

 

389

405

385

414

437

456

425

457

483

504

 

 

 

 

LO PR

110

117

128

137

117

124

136

144

121

129

141

150

127

136

 

148

158

133

142

155

165

138

147

160

171

 

 

 

 

MBh

52.3

53.4

57.1

61.0

51.0

52.2

55.7

59.6

49.8

50.9

54.4

58.2

48.6

49.7

 

53.1

56.7

46.2

47.2

50.4

53.9

42.8

43.7

46.7

49.9

 

 

 

 

S/T

0.86

0.81

0.66

0.49

0.89

0.84

0.68

0.51

0.91

0.86

0.70

0.52

0.94

0.89

 

0.72

0.54

0.98

0.92

0.75

0.56

0.99

0.93

0.75

0.56

 

 

 

1625

Delta T

25

24

21

17

26

25

21

17

26

25

21

17

26

25

 

22

17

26

25

21

17

24

23

20

16

 

 

 

KW

3.92

4.01

4.13

4.26

4.22

4.31

4.45

4.60

4.49

4.59

4.74

4.89

4.72

4.83

 

4.99

5.15

4.92

5.03

5.20

5.37

5.09

5.21

5.38

5.56

 

 

 

 

AMPS

18.6

18.9

19.4

20.0

19.7

20.1

20.7

21.3

21.1

21.5

22.1

22.8

22.3

22.7

 

23.4

24.1

23.5

23.9

24.6

25.4

24.6

25.1

25.9

26.7

 

 

 

 

HI PR

228

246

259

271

256

276

291

304

291

313

331

345

332

357

 

377

393

373

402

424

442

412

444

469

489

 

 

 

 

LO PR

107

114

124

133

113

120

131

140

118

125

137

146

124

131

 

144

153

129

138

150

160

134

142

156

166

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MBh

59.3

60.5

63.3

67.6

58.0

59.1

61.9

66.0

56.6

57.7

60.4

64.4

55.2

56.3

 

58.9

62.9

52.4

53.5

56.0

59.7

48.6

49.5

51.9

55.3

 

 

 

 

S/T

0.98

0.95

0.85

0.69

1.00

0.98

0.89

0.72

1.00

1.00

0.91

0.74

1.00

1.00

 

0.94

0.76

1.00

1.00

0.97

0.79

1.00

1.00

0.98

0.80

 

 

 

2085

Delta T

26

25

24

21

26

26

24

21

25

25

24

21

24

25

 

24

21

23

24

24

21

21

22

22

19

 

 

 

KW

4.08

4.17

4.30

4.44

4.40

4.50

4.64

4.79

4.68

4.78

4.94

5.10

4.93

5.03

 

5.20

5.38

5.13

5.25

5.42

5.61

5.32

5.44

5.62

5.81

 

 

 

 

AMPS

19.2

19.6

20.1

20.7

20.5

20.9

21.4

22.1

21.9

22.4

23.0

23.7

23.2

23.6

 

24.3

25.1

24.4

24.9

25.6

26.4

25.6

26.2

26.9

27.8

 

 

 

 

HI PR

240

258

273

284

269

290

306

319

306

330

348

363

349

375

 

396

414

392

422

446

465

434

467

493

514

 

 

 

 

LO PR

113

120

131

139

119

127

138

147

124

132

144

153

130

138

 

151

161

136

145

158

168

141

150

164

174

 

 

 

 

MBh

57.6

58.7

61.5

65.6

56.3

57.4

60.1

64.1

54.9

56.0

58.6

62.6

53.6

54.6

 

57.2

61.0

50.9

51.9

54.4

58.0

47.2

48.1

50.3

53.7

 

 

 

 

S/T

0.94

0.90

0.81

0.66

0.97

0.94

0.84

0.69

0.99

0.96

0.87

0.70

1.00

0.99

 

0.89

0.73

1.00

1.00

0.93

0.75

1.00

1.00

0.94

0.76

 

85

 

1850

Delta T

27

26

25

22

27

27

25

22

27

27

25

22

27

27

 

25

22

25

26

25

22

23

24

23

20

 

 

KW

4.05

4.14

4.27

4.41

4.36

4.46

4.60

4.75

4.64

4.74

4.90

5.06

4.88

4.99

 

5.16

5.33

5.09

5.21

5.38

5.56

5.27

5.39

5.57

5.76

 

 

 

 

AMPS

19.1

19.5

20.0

20.6

20.3

20.7

21.3

21.9

21.8

22.2

22.8

23.5

23.0

23.5

 

24.1

24.9

24.2

24.7

25.4

26.2

25.4

26.0

26.7

27.6

 

 

 

 

HI PR

238

256

270

282

267

287

303

316

303

326

345

359

345

372

 

393

409

389

418

442

461

429

462

488

509

 

 

 

 

LO PR

112

119

130

138

118

125

137

146

122

130

142

152

129

137

 

149

159

135

143

157

167

139

148

162

173

 

 

 

 

MBh

53.2

54.2

56.8

60.6

51.9

52.9

55.4

59.2

50.7

51.7

54.1

57.7

49.5

50.4

 

52.8

56.3

47.0

47.9

50.2

53.5

43.5

44.4

46.5

49.6

 

 

 

 

S/T

0.90

0.87

0.79

0.64

0.93

0.90

0.81

0.66

0.96

0.93

0.83

0.68

0.99

0.95

 

0.86

0.70

1.00

0.99

0.89

0.73

1.00

1.00

0.90

0.73

 

 

 

1625

Delta T

27

27

25

22

27

27

26

22

28

27

26

22

28

27

 

26

22

27

27

25

22

25

25

24

21

 

 

 

KW

3.95

4.04

4.17

4.30

4.26

4.35

4.49

4.64

4.53

4.62

4.78

4.93

4.76

4.87

 

5.03

5.20

4.96

5.07

5.24

5.42

5.14

5.25

5.43

5.61

 

 

 

 

AMPS

18.7

19.0

19.5

20.1

19.9

20.3

20.8

21.4

21.3

21.7

22.3

23.0

22.5

22.9

 

23.5

24.3

23.6

24.1

24.8

25.6

24.8

25.3

26.1

26.9

 

 

 

 

HI PR

231

248

262

273

259

278

294

307

294

317

334

349

335

361

 

381

397

377

406

428

447

416

448

473

494

 

 

 

 

LO PR

108

115

126

134

114

122

133

141

119

126

138

147

125

133

 

145

154

131

139

152

162

135

144

157

167

 

 

*

NOTE:

Shaded areas

is AHRI Rating Conditions

 

IDB: Entering Indoor

Dry Bulb Temperature

 

KW = Total system power

 

 

 

 

 

 

 

 

 

 

 

 

High and low pressures are measured at the liquid and suction access fittings.

 

 

 

 

AMPS: Unit amps (comp.+ evaporator + condenser fan motors)

 

 

 

 

 

 

COOLING PERFORMANCE DATA

GPC1360H41BA

Page 25
Image 25
Goodmans GPC1324H41A COOLING PERFORMANCE DATA GPC1360H41BA, Expanded Performance Data, MODEL GPC1360H41, Cooling Operation

FAQ

What are the design subcooling and superheat values for the GPC1360H41** model?

The design subcooling is 123 F at the liquid access fitting connection, and the design superheat is 83 F at the compressor suction access fitting connection.

What are the outdoor ambient temperature conditions for the GPC1360H41** model?

The outdoor ambient temperature conditions range from 65 to 115 degrees Fahrenheit.

How is the cooling performance measured for the GPC1360H41** model?

The cooling performance is measured in terms of air temperature, airflow, power consumption, and high and low pressures at the access fittings.