Goodmans GPC 13 SEER R-410A Package Cooling Specifications, Models, Coils, GPC1342H41AB

Models: GPC1324H41A GPC 13 SEER R-410A

1 47
Download 47 pages 14.36 Kb
Page 32
Image 32
PACKAGE COOLING SPECIFICATIONS

PACKAGE COOLING SPECIFICATIONS

COILS

 

 

 

 

GPC1342H41AB

 

CAPACITY

 

SEER

13.0

 

 

 

 

COOLING

 

COOLING CAPACITY, BTUH

41,000

5MM

 

UNIT

 

VOLTAGE (NAMEPLATE)

208-230/1/60

 

ELECTRICAL

 

AMPS (TOTAL)

22.17

WITH

 

SPECIFICATION

 

MINIMUM CIRCUIT AMPACITY

26.6

 

 

 

 

 

 

 

MAXIMUM OVERCURRENT PROTECTION (1)

40

MODELS

 

COMPRESSOR

 

TYPE

SCROLL

 

 

 

RATED LOAD AMPS

17.9

 

 

 

LOCKED ROTOR AMPS

112

 

CONDENSER

 

HORSEPOWER

1/4

 

 

FAN MOTOR

 

RPM

1075

 

 

 

 

FULL LOAD AMPS

1.4

 

 

 

 

LOCKED ROTOR AMPS

2.9

 

 

CONDENSER FAN

 

BLADE DIAMETER (INCHES) /# OF BLADES

22 / 4

 

 

CONDENSER

 

FACE AREA - SQ. FT.

16.0

 

 

COIL

 

NUMBER OF ROWS

1

 

 

 

 

FINS PER INCH

28

 

 

EVAPORATOR

 

HORSEPOWER - NO. OF SPEEDS

1/2 - 3

 

 

BLOWER

 

FULL LOAD AMPS

2.87

 

 

MOTOR

 

LOCKED ROTOR AMPS

4.9

 

 

 

 

MOTOR SPEED TAP - COOLING

LOW

 

 

 

 

RPM

1075

 

 

EVAPORATOR

 

DIAMETER X WIDTH (INCHES)

10 x 8

 

 

BLOWER

 

RATED SCFM COOLING

1,410

 

 

 

 

MAX EXTERNAL STATIC PRESS ("w.c.)

0.5

 

 

EVAPORATOR

 

FACE AREA - SQ. FT.

6.2

 

 

COIL

 

NUMBER OF ROWS

4

 

 

 

 

FINS PER INCH

14

 

 

GENERAL

 

FILTER SIZE - SQ. FT. *

(2) 20 x 20 x 1

 

 

INFORMATION

 

DRAIN SIZE (INCHES)

3/4"

 

 

 

 

EXPANSION DEVICE

ORIFICE (0.072)

 

 

 

 

REFRIGERANT CHARGE R-410A (Oz.)

88

 

 

 

 

POWER SUPPLY CONDUIT KNOCKOUT SIZE (IN.)

3/4, 1, 1-1/4

 

 

 

 

LOW VOLTAGE CONDUIT KNOCKOUT SIZE (IN.)

1/2

 

 

 

 

SHIPPING WEIGHT LBS.

370

 

 

 

 

OPERATING WEIGHT LBS.

360

 

 

 

 

 

 

 

GPC1342H41AB

 

GPC1349H41AA

 

GPC1360H41BB

GPC1349H41AA

GPC1360H41BB

45,500

57,500

13.013.0

208-230/1/60 208-230/1/60

24.17

33.6

29.2

40.2

45

60

SCROLL

SCROLL

19.9

26.4

109

134

1/4

1/4

1075

1075

1.4

1.4

2.9

2.9

22 / 4

22 / 4

16.0

19.5

1

1

28

28

1/2 - 3

3/4 - 3

2.87

5.8

4.9

NA

MEDIUM

T2

1075

1075

10 x 8

11 x 8

1,585

1,850

0.5

0.5

6.2

7.0

4

4

14

14

(2) 20 x 20 x 1

(2) 20 x 25 x 1

3/4"

3/4"

ORRIFICE (0.078)

ORIFICE (0.088)

80

93

3/4, 1, 1-1/4

3/4, 1, 1-1/4

1/2

1/2

400

400

390

390

(1)Maximum Overcurrent Protection Device: MUST use Time Delay Fuse or HACR type Circuit Breaker of the same size as noted. * Calculated external filter size based on air velocity of 300 ft/min.

Wire size should be determined in accordance with National Electrical Codes. Extensive wire runs will require larger wire sizes.

Unit specifications are subject to change without notice. ALWAYS refer to the units serial plate for the most up-to-date general and electrical information.

IMPORTANT: While this data is presented as a guide, it is important to electrically connect the unit and properly size wires and fuses/circuit breakers in accordance with the National Electrical Code and/or all local codes. Data shown is w/o electric heaters.

32

Page 32
Image 32
Goodmans GPC 13 SEER R-410A Package Cooling Specifications, Models, Coils, GPC1342H41AB, GPC1349H41AA, GPC1360H41BB

FAQ

What is the cooling capacity of the GPC1342H41AB model?

The cooling capacity of the GPC1342H41AB model is 41,000 BTUH.

What is the voltage nameplate for the unit?

The voltage nameplate for the unit is 208-230/1/60.

What is the packed shipping weight of the unit?

The packed shipping weight of the unit is 370 lbs.