Goodmans GPC 13 SEER R-410A, GPC1324H41A Package Cooling Specifications, GPC1336-42H41AA

Models: GPC1324H41A GPC 13 SEER R-410A

1 47
Download 47 pages 14.36 Kb
Page 12
Image 12

PACKAGE COOLING SPECIFICATIONS

GPC13[36-42]H41AA

 

 

 

 

GPC1336H41*

GPC1342H41*

 

 

 

 

 

 

 

 

 

COOLING

COOLING CAPACITY, BTUH

 

36,000

41,000

 

 

CAPACITY

SEER

 

13.0

13.0

 

 

 

 

 

 

 

 

 

UNIT

VOLTAGE (NAMEPLATE)

 

208-230/1/60

208-230/1/60

 

 

ELECTRICAL

AMPS (TOTAL)

 

20.06

22.2

 

 

SPECIFICATION

MINIMUM CIRCUIT AMPACITY

 

24.2

26.6

 

 

 

MAXIMUM OVERCURRENT PROTECTION (1)

 

40

40

 

 

COMPRESSOR

TYPE

 

SCROLL

SCROLL

 

 

 

RATED LOAD AMPS

 

16.7

17.9

 

 

 

LOCKED ROTOR AMPS

 

79

112

 

 

 

 

 

 

 

 

 

CONDENSER

HORSEPOWER

 

1/4

1/4

 

 

FAN MOTOR

RPM

 

830

1075

 

 

 

FULL LOAD AMPS

 

1.5

1.4

 

 

 

LOCKED ROTOR AMPS

 

3.0

2.9

 

 

 

 

 

 

 

 

 

CONDENSER FAN

BLADE DIAMETER (INCHES) / # OF BLADES

 

22 / 4

22 / 4

 

 

 

 

 

 

 

 

 

CONDENSER

FACE AREA - SQ. FT.

 

13.4

17.0

 

 

COIL

NUMBER OF ROWS

 

1

1

 

 

 

FINS PER INCH

 

24

24

 

 

 

 

 

 

 

 

 

EVAPORATOR

HORSEPOWER - NO. OF SPEEDS

 

1/3 - 3

1/2 - 3

 

 

BLOWER

FULL LOAD AMPS

 

1.86

2.87

 

 

MOTOR

LOCKED ROTOR AMPS

 

3.2

4.9

 

 

 

MOTOR SPEED TAP - COOLING

 

LOW

LOW

 

 

 

RPM

 

1075

1075

 

 

 

 

 

 

 

 

 

EVAPORATOR

DIAMETER X WIDTH (INCHES)

 

9 x 8

10 x 8

 

 

BLOWER

RATED SCFM COOLING

 

1,205

1,410

 

 

 

MAX EXTERNAL STATIC PRESS ("w.c.)

 

0.5

0.5

 

 

 

 

 

 

 

 

 

EVAPORATOR

FACE AREA - SQ. FT.

 

5.2

6.2

 

 

COIL

NUMBER OF ROWS

 

3

4

 

 

 

FINS PER INCH

 

14

14

 

 

 

 

 

 

 

 

 

GENERAL

FILTER SIZE - SQ. FT. *

 

25 x 25 x 1

(2) 20 x 20 x 1

 

 

INFORMATION

DRAIN SIZE (INCHES)

 

3/4"

3/4"

 

 

 

EXPANSION DEVICE

ORIFICE (0.065)

ORIFICE (0.072)

 

 

 

REFRIGERANT CHARGE R-410A (Oz.)

 

85

105

 

 

 

POWER SUPPLY CONDUIT KNOCKOUT SIZE (IN.)

 

3/4, 1, 1-1/4

3/4, 1, 1-1/4

 

 

 

LOW VOLTAGE CONDUIT KNOCKOUT SIZE (IN.)

 

1/2

1/2

 

 

 

SHIPPING WEIGHT LBS.

 

370

370

 

 

 

OPERATING WEIGHT LBS.

 

360

360

 

 

 

 

 

 

 

 

(1)Maximum Overcurrent Protection Device: MUST use Time Delay Fuse or HACR type Circuit Breaker of the same size as noted. * Calculated external filter size based on air velocity of 300 ft/min.

Wire size should be determined in accordance with National Electrical Codes. Extensive wire runs will require larger wire sizes.

Unit specifications are subject to change without notice. ALWAYS refer to the units serial plate for the most up-to-date general and electrical information.

IMPORTANT: While this data is presented as a guide, it is important to electrically connect the unit and properly size wires and fuses/circuit breakers in accordance with the National Electrical Code and/or all local codes. Data shown is w/o electric heaters.

12

Page 12
Image 12
Goodmans GPC 13 SEER R-410A, GPC1324H41A service manual Package Cooling Specifications, GPC1336-42H41AA

FAQ

What is the cooling capacity of the GPC1336H41 air conditioner?

The cooling capacity of GPC1336H41 is 36,000 BTUH.

What is the SEER rating of the GPC1342H41 air conditioner?

The SEER rating of GPC1342H41 is 13.0.

What is the recommended filter size for the GPC 13 SEER R-410A Air Conditioner?

The recommended filter size for this air conditioner is 25 x 25 x 1 square feet.