COOLING PERFORMANCE DATA

PERFORMANCE TEST

All data based upon listed indoor dry bulb temperature. .00 inches external static pressure on coil of outdoor section. Indoor air cubic feet per minute (CFM) as listed in the Performance Data Sheets:

If conditions vary from this, results will change as follows:

1.As indoor dry bulb temperatures increase, a slight increase will occur in indoor air temperature drop (Delta T). Low and high side pressures and power will not change.

2.As indoor CFM decreases, a slight increase will occur in indoor temperature drop (Delta T). A slight decrease will occur in low and high side pressures and power.

A properly operating unit should be within plus or minus 3 degrees of the typical (Delta T) value shown. A properly operating unit should be within plus or minus 7 PSIG of the HI PR shown.

A properly operating unit should be within plus or minus 3 PSIG of the LO PR shown.

A properly operating unit should be within plus or minus 3 Amps of the typical value shown.

45

Page 45
Image 45
Goodmans GPC1324H41A, GPC 13 SEER R-410A service manual Cooling Performance Data, Performance Test

FAQ

What factors affect indoor temperature drop?

Indoor dry bulb temperatures and CFM can affect the indoor temperature drop. As indoor dry bulb temperatures increase, a slight increase will occur in indoor air temperature drop. As indoor CFM decreases, a slight increase will occur in indoor temperature drop.

What are the typical values for a properly operating unit?

A properly operating unit should be within plus or minus 3 degrees of the typical Delta T value shown. It should also be within plus or minus 7 PSIG of the HI PR shown, within plus or minus 3 PSIG of the LO PR shown, and within plus or minus 3 Amps of the typical value shown.

How do different conditions affect cooling performance?

If conditions vary from the listed indoor dry bulb temperature and CFM, results will change. This includes changes in indoor air temperature drop, low and high side pressures, and power.